The soybean-oil-based insulating fluid to IEC 62770, IEEE C57.147 and ASTM D6871 with a fire point of 350–360 °C – for distribution and power transformers and retrofilling.

At a glance
Product typenatural ester (vegetable-oil-based insulating fluid), formerly “Envirotemp FR3”
BaseSoybean oil; according to Cargill > 99 % bio-based to ASTM D6866; additives below 2 %
StandardsASTM D6871, IEEE C57.147, IEC 62770; K-class; FM Global approved, UL classified (according to Cargill)
ApplicationsDistribution and power transformers, retrofilling, data centres, wind, solar, battery storage, traction
Transformer designhermetically sealed; free-breathing only with limited air ingress
Classificationnot classified as hazardous under CLP; AwSV (Germany): generally hazardous to water (awg); not dangerous goods for transport
Pack sizes1 l, 8 l, 20 l, 25 l, drum (200 l), IBC (1,000 l), road tanker – availability on request

What sets Cargill FR3 apart

FR3 is the oldest and most widely used natural ester for transformers. Cargill cites more than 30 years of service experience and more than five million transformers filled with it worldwide (as of 2026). The product was launched in 1998, at that time under the name Envirotemp FR3; in 2012 Cargill fully took over the business and the brand.

Fire safety

With a fire point of 350–360 °C, FR3 is well above the 300 °C threshold of the K-class. Mineral oil typically has a fire point of around 170 °C. According to Cargill, FR3 is FM Global approved and UL classified as a less-flammable dielectric fluid – relevant for insurers and fire safety requirements.

Moisture and paper insulation

Natural esters absorb considerably more water than mineral oil and draw moisture out of the paper. Cargill states that transformers with FR3 and thermally upgraded paper can be operated at top-oil temperatures of up to 140 °C and achieve up to 20 % more loading capability than with mineral oil without shortening their service life (manufacturer’s data, with reference to IEC 60076-14 or IEEE C57.154).

Low temperatures

The pour point is −21 °C. According to Cargill, FR3 retains its dielectric properties down to −50 °C; for cold starts, Cargill recommends preheating the top oil to −10 to 0 °C and blocking tap-changers at oil temperatures below −10 °C.

Typical properties

PropertyTest methodLimit IEC 62770:2013Typical FR3
Fire pointISO 2592> 300 °C350–360 °C
Flash point (Pensky-Martens)ISO 2719≥ 250 °C260–270 °C
Pour pointISO 3016≤ −10 °C−21 °C
Density at 20 °CISO 3675≤ 1.0 g/cm³0.92 g/cm³
Viscosity at 40 °CISO 3104≤ 50 mm²/s32–34 mm²/s
Viscosity at 100 °CISO 3104≤ 15 mm²/s7.7–8.3 mm²/s
Viscosity at 0 °CASTM D445–190 mm²/s
Breakdown voltage (2.5 mm)IEC 60156≥ 35 kV70–80 kV
Dissipation factor at 90 °CIEC 60247≤ 0,050,01–0,03
Water contentIEC 60814≤ 200 mg/kg4–50 mg/kg
AcidityIEC 62021-3≤ 0.06 mg KOH/g0.01–0.05 mg KOH/g
Corrosive sulphurIEC 62697 / ASTM D1275non-corrosivenon-corrosive
PCBIEC 61619free from PCBnot detectable
AdditivesIEC 60666max. 5 %< 2 %
Oxidation IEC 61125 C (48 h, 120 °C): acidity / viscosity increase / DDFIEC 61125≤ 0,6 / ≤ 30 % / ≤ 0,50,1–0,3 / 17–23 % / 0,1
Oxidation induction time (130 °C)ASTM D6186–62 min
Gassing tendencyASTM D2300≤ 0 (ASTM D6871)−79

Typical values according to the Cargill FR3 R2000 technical data sheet (©2026), cross-checked with the FR3 brochure (©2025). According to Cargill, typical values are not acceptance values.

Storage and handling

  • Store in labelled, tightly closed containers at 10–40 °C in a dry place; do not keep drums and IBCs outdoors.
  • Use a dry nitrogen blanket in storage tanks, do not vent to atmosphere, no free-breathing tanks; keep opened containers under nitrogen.
  • Use dedicated equipment for storage, transfer and processing.
  • Thin films polymerise in air over time; do not leave components impregnated with FR3 exposed to air for long periods. Porous materials soaked with FR3 (rags, absorbents) can self-heat.
  • FR3 is miscible with mineral oil, but not with silicone oil.

Retrofilling: from mineral oil to FR3

FR3 is frequently used to retrofill existing mineral oil transformers. Cargill recommends no more than 7 % residual mineral oil; typically 3–5 % remains. Higher proportions can lower the fire point below 300 °C. For power transformers above 138 kV, Cargill recommends a design review beforehand. We support retrofills with material compatibility tests, analyses in our own laboratory and checks after conversion – more in Topping up, mixing and retrofilling.

Ester fluids from Vielhauer GmbH

  • Delivery across Europe with our own logistics – 1 l, 8 l, 20 l, 25 l, drums (200 l), IBCs (1,000 l) and bulk by road tanker; availability and lead time on request
  • Our own laboratory for ester fluids: oil analyses, miscibility analyses and material compatibility tests
  • Retrofilling support from sampling through to the check after conversion
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request
  • Pack sizes, delivery and how to order: Buy FR3, FR3r and SE3

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Frequently asked questions

Which standards does Cargill FR3 meet?

FR3 is specified to ASTM D6871, IEEE C57.147 and IEC 62770. Cargill describes FR3 as a K-class fluid (fire point above 300 °C); according to Cargill, it is FM Global approved and UL classified as a less-flammable dielectric fluid.

Can FR3 be used in free-breathing transformers?

Cargill recommends FR3 for hermetically sealed transformers. According to Cargill, free-breathing transformers can be filled with FR3 if a system limits the exchange of air above the fluid. For free-breathing equipment without such measures, a synthetic ester such as SE3 is the obvious choice.

How much mineral oil may remain when retrofilling with FR3?

Cargill recommends no more than 7 % residual mineral oil; typically 3–5 % remains. More than 7 % mineral oil can lower the fire point below 300 °C. For power transformers above 138 kV, Cargill recommends a design review beforehand.

How should FR3 be stored?

In tightly closed, labelled containers at 10–40 °C, in a dry place and not outdoors. Use a dry nitrogen blanket in storage tanks and do not vent to atmosphere; keep opened drums and IBCs under nitrogen as well. Cargill recommends dedicated equipment, pumps and hoses for FR3.

Is FR3 biodegradable?

In its technical data sheet (R2000, 2026), Cargill states that FR3 is readily biodegradable, with reference to OECD 301 B, C or F or EPA OPPTS 835.3110. The German version of the safety data sheet from 2023 contains no data on biodegradability. For tenders, we recommend using the information in the current data sheet together with the test method.

What is the water hazard class of FR3?

FR3 consists mainly of soybean oil, a floating liquid substance officially published by the German Environment Agency (Umweltbundesamt) under Kenn-Nr. 9442. Under the AwSV (German Ordinance on Facilities for Handling Substances Hazardous to Water), such substances are considered generally hazardous to water (awg); the Cargill safety data sheets state this accordingly. Under § 13(1) AwSV, the facility requirements then only apply if entry into a surface water body cannot be ruled out.

More on this topic

FR3™, FR3r™ and SE3™ are trademarks of Cargill, Incorporated; Shell MIDEL is a trademark of Shell Brands International AG. The trademarks are used here solely to identify the original products. Vielhauer GmbH is an independent dealer. All technical data are typical values from the manufacturers’ documentation (as of October 2026) and do not constitute a specification; the current data sheet applies.