Cargill’s synthetic ester to IEC 61099 – K-class, pour point below −50 °C and, according to Cargill, suitable for free-breathing transformers.
| At a glance | |
|---|---|
| Product type | synthetic ester (insulating fluid) |
| Standard | IEC 61099; K-class (fire point > 300 °C) |
| Distinctive feature | suitable for free-breathing transformers according to Cargill; pour point below −50 °C; oxidation test over 800 h |
| Applications | Transformers in cold climates, free-breathing transformers, special applications |
| Classification | not a hazardous mixture under CLP (SDS 07/2025); not dangerous goods for transport; WGK (German water hazard class) on request |
| Pack sizes | 1 l, 8 l, 20 l, 25 l, drum (200 l), IBC (1,000 l), road tanker – availability on request |
With SE3, Cargill adds a synthetic ester to its natural esters FR3 and FR3r. The key difference: synthetic esters age considerably more slowly in air. Cargill therefore explicitly describes SE3 as suitable for free-breathing transformers – that is, equipment with an open conservator, in which natural esters should only be used with additional measures against air ingress.
In the oxidation test to IEC 61125, IEC 61099 requires a test duration of 164 hours. According to Cargill, SE3 was tested for 800 hours and then reached a total acidity of 0.11 mg KOH/g with less than 0.01 % sludge. Added to this is its low-temperature behaviour: the pour point is below −50 °C, and at −20 °C the viscosity is 1,200 mm²/s.
| Property | Test method | Limit IEC 61099 | Typical SE3 |
|---|---|---|---|
| Fire point | ISO 2592 | ≥ 300 °C | > 305 °C |
| Flash point | ISO 2719 | ≥ 250 °C | > 260 °C |
| Pour point | ISO 3016 | ≤ −45 °C | < −50 °C |
| Density at 20 °C | ISO 3675 | ≤ 1,000 kg/m³ | 960–970 kg/m³ |
| Viscosity at 40 °C | ISO 3104 | ≤ 35 mm²/s | 28 mm²/s |
| Viscosity at 100 °C | ISO 3104 | ≤ 15 mm²/s | 6 mm²/s |
| Viscosity at −20 °C | ISO 3104 | ≤ 3,000 mm²/s | 1,200 mm²/s |
| Breakdown voltage | IEC 60156 | ≥ 45 kV (untreated) | > 65 kV |
| Dissipation factor at 90 °C | IEC 60247 | ≤ 0,03 | 0,01 |
| DC resistivity at 90 °C | IEC 60247 | ≥ 2 GΩm | 60 GΩm |
| Water content | IEC 60814 | ≤ 200 mg/kg | ≤ 100 mg/kg |
| Acidity | IEC 62021 | ≤ 0.03 mg KOH/g | 0.01–0.02 mg KOH/g |
| Oxidation IEC 61125 C, 164 h: acidity / sludge | IEC 61125 | ≤ 0,3 / ≤ 0,01 % | 0,02 / < 0,01 % |
| Oxidation 800 h: acidity / sludge | IEC 61125 | – | 0,11 / < 0,01 % |
Typical values according to the SE3 brochure (©2026) and the SE3 data sheet (©2025). For breakdown voltage, the two documents state “> 65 kV” and “> 70 kV” respectively. Typical values are not a specification.
| SE3 (synthetic) | FR3 / FR3r (natural) | |
|---|---|---|
| Standard | IEC 61099 | IEC 62770 |
| Free-breathing transformers | suitable according to Cargill | only with limited air ingress (FR3) |
| Pour point | < −50 °C | −21 °C / −33 °C |
| Viscosity at 40 °C | 28 mm²/s | 32–34 / 37 mm²/s |
| Fire point | > 305 °C | 350–360 °C |
For an overview of all three Cargill products, see Ester fluids compared. We check in our own laboratory whether SE3 is compatible with your existing fluid or your materials.
Ester fluids from Vielhauer GmbH
Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.
SE3 is Cargill’s synthetic ester to IEC 61099, a K-class fluid with a fire point above 305 °C. Cargill describes it as optimised for extreme cold and suitable for free-breathing transformers. The documentation dates from 2025.
Synthetic esters are considerably more resistant to oxidation than natural esters. According to Cargill, SE3 passed the oxidation test to IEC 61125 not just for the required 164 hours but for 800 hours (total acidity 0.11 mg KOH/g, sludge below 0.01 %).
Cargill states a pour point below −50 °C (product overview: −54 °C, safety data sheet: −57 °C) and a viscosity of 1,200 mm²/s at −20 °C. IEC 61099 allows up to 3,000 mm²/s at −20 °C.
In the data sheet, Cargill states “readily biodegradable to OECD 301 B”. The safety data sheet (version 1.0 of 31 July 2025) reports 73 % degradation to OECD 301 F. For tenders, we recommend using the information in the current safety data sheet.
FR3™, FR3r™ and SE3™ are trademarks of Cargill, Incorporated; Shell MIDEL is a trademark of Shell Brands International AG. The trademarks are used here solely to identify the original products. Vielhauer GmbH is an independent dealer. All technical data are typical values from the manufacturers’ documentation (as of October 2026) and do not constitute a specification; the current data sheet applies.
Vielhauer GmbH, Siemensstr. 11 A, 51381 Leverkusen
+49(0)2236 – 322450
info@mv-lub.de