Fire point, moisture tolerance, viscosity and limits of use: what distinguishes mineral transformer oil from ester fluids and when each solution makes sense.
For oil-filled transformers there are now two large families of insulating liquids to choose from: proven mineral oil to IEC 60296 and ester fluids – synthetic esters to IEC 61099 and natural esters to IEC 62770. As a supplier of both families, we compare them here on purely technical grounds.
| Characteristic | Mineral oil | Synthetic ester | Natural ester |
|---|---|---|---|
| Standard | IEC 60296 | IEC 61099 | IEC 62770 |
| Fire class (IEC 61039) | O (fire point ≤ 300 °C) | K (fire point > 300 °C) | K (fire point > 300 °C) |
| Typical flash/fire point | approx. 150 / 170 °C; Shell Diala S4 ZX-I: flash point 191 °C | approx. 260 / 316 °C | approx. 316 / 360 °C |
| Viscosity at 40 °C | below 12 mm²/s (S4 ZX-I: 9.8) | approx. 29 mm²/s | approx. 32–37 mm²/s |
| Pour point | below −40 °C | below −45 °C | higher than for mineral oil, depending on the product about −10 to −30 °C |
| Water saturation at 20 °C | approx. 55 ppm | approx. 2,600 ppm | approx. 1,100 ppm |
| Use in free-breathing transformers | yes | yes | only hermetically sealed or with membrane |
Typical values from technical literature (including the University of Stuttgart and CIGRE) and manufacturers’ data; individual products differ.
Mineral oils belong to class O, esters with a fire point above 300 °C to class K (“less flammable”). Where transformers are installed in buildings, tunnels, wind turbines or densely built-up areas, fire safety regulations or insurers often require class K fluids.
Esters dissolve many times more water. Absolute water limits for mineral oil therefore cannot be applied to esters – what matters is the relative saturation. Separate guidelines apply to the assessment of ester samples, for example IEC 62975 for natural esters.
Mineral oil is considerably less viscous and transfers heat better for the same design. Esters may require additional cooling ducts. At very low temperatures, mineral oils and synthetic esters have advantages over natural esters.
Mineral oil is the standard solution proven over decades, with the most manufacturer approvals and the lowest price per litre. Esters have long been used in special transformers (rail, wind) and increasingly in distribution and power transformers.
An existing mineral oil transformer can be converted to ester. Residual mineral oil has to be minimised and the compatibility of all materials checked – more in Topping up and mixing and at mv-lub.eu/retrofilling. We support you with material compatibility tests and analyses in our own laboratory.
Transformer oil from Vielhauer GmbH
Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.
Yes, this is called retrofilling. The mineral oil is removed as far as possible, because residues lower the fire point of the ester fluid, and bushings, tap-changers and gaskets are checked for compatibility. Because of the higher viscosity of esters, cooling also has to be assessed.
Where fire safety regulations or insurers require less flammable fluids, class K fluids to IEC 61039 are often used, i.e. with a fire point above 300 °C – these are esters and silicone oils. Mineral oils belong to class O. Which requirements apply is determined by local regulations and the operator.
Per litre, usually yes. Depending on the project, this is offset by lower structural fire protection requirements and higher moisture tolerance. We advise you on both options.
Shell, Diala and Shell MIDEL are trademarks of Shell Brands International AG. They are used here solely to identify the original products. Vielhauer GmbH sells Shell Diala products as an independent dealer. TotalEnergies and ISOVOLTINE are trademarks of TotalEnergies SE. All technical data are typical values from the manufacturers’ data sheets (as of October 2026) and do not constitute a specification; the current data sheet applies.