Ester retrofill: converting a transformer to natural ester

In an ester retrofill, a mineral oil transformer is converted to natural or synthetic ester – here you can read which requirements apply according to Cargill, what the procedure looks like and what to look out for with FR3, FR3r and SE3.

Ester retrofill: what converting to natural ester involves

Retrofilling means replacing the insulating liquid of an existing transformer – usually mineral transformer oil with a natural ester such as Cargill FR3 or FR3r or a synthetic ester such as Cargill SE3. Cargill distinguishes between the terms: retrofilling involves changing the fluid and carrying out minor work such as replacing gaskets, while retrofitting additionally involves replacing or overhauling components.

Anyone planning to convert a transformer to natural ester needs to answer three questions: Is the unit suitable? How much mineral oil may remain? How is the new fluid filled and then monitored?

Reasons for converting

  • Fire safety: esters have a fire point above 300 °C and are K-class under IEC 61039, whereas mineral oil is O-class. According to Cargill, this can reduce the effort required for fire protection measures and clearances; what applies in each individual case is determined by regulations, insurers and operators. More in Fire safety with ester fluids.
  • Moisture: according to Cargill, the water saturation point of FR3 is around ten times higher than that of mineral oil. The ester absorbs moisture from the paper insulation.
  • Loading capability: for retrofills with FR3, Cargill cites up to 15 % more loading capability without further modifications; the operating temperature may rise by around 5 °C and remain within the usual range (manufacturer’s information).

Prerequisites

Condition and design

Cargill recommends assessing the condition of the transformer beforehand and resolving any existing technical problems before retrofilling. According to IEC 62975, natural esters are intended for equipment in which the fluid is not permanently in contact with ambient air: hermetically sealed transformers, conservators with an air bag or membrane, and units with a nitrogen blanket. According to Cargill, free-breathing transformers can be retrofilled with FR3 if a system limits the air exchange above the fluid.

Voltage level

According to Cargill, retrofilling with FR3 is typically possible up to 138 kV without internal modifications, and derating of the voltage class is not necessary. For large power transformers above 138 kV, Cargill recommends a design review beforehand.

Materials and gaskets

Cargill recommends replacing all gaskets in contact with the fluid – with higher-nitrile NBR, silicone or fluoropolymer (Viton), and with silicone or fluoropolymer at higher temperatures. Oil-impregnated bushings remain tightly sealed with their original fluid. According to Cargill, tap changers can operate in FR3, with vacuum-type tap changers preferred; some manufacturers require additional safety margins. Approval by the transformer and component manufacturers is therefore part of the preparation.

Residual mineral oil, silicone oil and PCBs

Cargill recommends no more than 7 % residual mineral oil; typically 3–5 % remains. More than 7 % mineral oil can lower the fire point below 300 °C and thus jeopardise the K-class rating. FR3 is miscible with mineral oil, but not with silicone oil: according to Cargill, transformers that previously contained silicone oil should not be filled with FR3. For old units, the existing oil should be tested for PCBs before disposal – see AwSV and disposal (Germany).

Step-by-step procedure

The steps follow Cargill’s guides for distribution transformers (R2010, up to 7,500 kVA and 25 kV) and power transformers (R2040). The transformer manufacturer’s specifications and the on-site safety rules are authoritative.

  1. Preparation: obtain the nameplate data and maintenance instructions, clarify the permissible tank vacuum and de-energise the unit. Earth the transformer, pumps and tanks – according to Cargill, flowing ester can build up a strong static charge.
  2. Sampling: before retrofilling, take a sample for oil analysis and dissolved gas analysis; it provides the baseline values.
  3. Assessment: evaluate the results, clarify material compatibility and miscibility, and obtain the manufacturers’ approvals.
  4. Draining: pump out the oil or – if the tank is level or inclined towards the drain – push it out with dry gas at around 34 kPa (5 psig); drain the radiators completely.
  5. Dripping and flushing: allow to drip for at least half an hour, preferably two hours; a vacuum within the tank limit speeds this up. Then flush with around 5 % of the fill volume of hot FR3 (50–80 °C) at low pressure, including the radiators, allow to drip again and remove the residue.
  6. Replacing gaskets: renew the gaskets in contact with the fluid and tighten them as appropriate for the material.
  7. Filling, vacuum and degassing: Cargill recommends filling from the bottom under vacuum within the tank limit, with a fluid temperature of at least 50 °C and 0.5 µm filters. For degassing, Cargill gives 60–65 °C at the lowest possible pressure, typically below 100 Pa. According to Cargill, atmospheric filling is typically only acceptable up to 69 kV. Bulk fluid from the road tanker must be heated and filtered before filling.
  8. Completion: establish a gas blanket of dry air or nitrogen at 13–20 kPa (2–3 psig), check for leaks and attach a retrofill label with the batch number.
  9. Standing time: before energising, wait until gas bubbles have escaped – according to Cargill, preferably 24 hours, depending on the filling temperature. Take a new baseline sample before energising.
  10. Energising: energise power transformers initially without load, apply load after three hours at the earliest and watch for leaks.
  11. Checks: check the temperature and pressure the following day and record the tank pressure regularly – according to Cargill, if it remains constant at 0 despite temperature changes, this indicates a leak. Take another sample after six months.

A note on diagnostics: according to Cargill, the insulation power factor of FR3-filled transformers is higher than with mineral oil. After a retrofill, the new value only settles gradually, because the mineral oil in the paper is only replaced little by little. How ester samples are evaluated is explained in Oil analysis for ester-filled transformers.

Retrofill checklist

Check itemWhat to look out for
Designhermetically sealed, membrane or nitrogen blanket; free-breathing with FR3 only with limited air ingress
Voltage leveldesign review above 138 kV according to Cargill
Conditionbaseline analysis and dissolved gas analysis; resolve known faults beforehand
Previous fillingmineral oil: residue ≤ 7 %; previously silicone oil: no retrofill with FR3; old units: PCB analysis
Gasketshigher-nitrile NBR, silicone or fluoropolymer; replace all in contact with the fluid
Bushings, tap changersmanufacturer’s approval; keep oil-impregnated bushings sealed
Cooling and coldhigher viscosity; pour point FR3 −21 °C, FR3r −33 °C, SE3 below −50 °C
Fillingvacuum, at least 50 °C, 0.5 µm filter, degassing according to the manufacturer’s specifications
Authorities, insurersfire protection requirements; AwSV classification of the mixture of ester and residual mineral oil (Germany)
Follow-up checksample before energising and after six months; pressure and temperature

On the AwSV (German Ordinance on Facilities for Handling Substances Hazardous to Water): natural esters are considered generally hazardous to water (awg). § 13 AwSV provides relief for floating substances and mixtures consisting exclusively of such substances; whether this applies to an ester with residual mineral oil should be clarified with the competent authority.

SE3 or FR3/FR3r: what to look out for when retrofilling

FR3 is the product for which Cargill publishes the retrofilling guides R2010 and R2040 and the figures of 7 % residual mineral oil and 138 kV. FR3r is also a natural ester to IEC 62770, with a lower pour point (−33 °C). We have not found a separate retrofilling guide for FR3r in Cargill’s documentation; you should have the FR3 values confirmed for FR3r. Cargill’s FR3r documentation makes no statement on free-breathing transformers.

SE3 is a synthetic ester to IEC 61099 and, according to Cargill, suitable for free-breathing transformers – limiting air ingress is then not required. However, IEC 61203 points out that synthetic esters should only be used in transformers whose internal insulation is designed for them; the standard only covers retrofill mixtures in an informative annex. Cargill does not give a limit for residual mineral oil in the SE3 documentation. Because the fire point of SE3, at above 305 °C, is closer to the 300 °C limit than that of FR3 (350–360 °C), the permissible residual quantity should be clarified beforehand and the fire point of the mixture checked.

How Vielhauer supports your retrofill

The work on the transformer is carried out by your service partner or your own maintenance team. We support the project from sampling through to the check after conversion:

  • Oil analyses of the existing fluid in our own laboratory, plus miscibility analyses and material compatibility tests for gaskets and materials
  • Delivery of Cargill FR3, FR3r or SE3 in 200 l drums, 1,000 l IBCs or in bulk by road tanker – across Europe with our own logistics; availability and lead time on request (pack sizes and delivery)
  • Analyses after filling and after six months to check the conversion
  • technical data sheets and safety data sheets on request; free qualification programmes for equipment

This gives you reliable baseline values, a delivery quantity that covers flushing and filling, and a documented check after conversion. For planning purposes, all we need initially is the nameplate data, the fill volume and a sample of the existing oil.

Ester fluids from Vielhauer GmbH

  • Delivery across Europe with our own logistics – 1 l, 8 l, 20 l, 25 l, drums (200 l), IBCs (1,000 l) and bulk by road tanker; availability and lead time on request
  • Our own laboratory for ester fluids: oil analyses, miscibility analyses and material compatibility tests
  • Retrofilling support from sampling through to the check after conversion
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request
  • Pack sizes, delivery and how to order: Buy FR3, FR3r and SE3

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Frequently asked questions

How much mineral oil may remain when retrofilling with ester?

For FR3, Cargill recommends no more than 7 % residual mineral oil; typically 3–5 % remains. More than 7 % mineral oil can lower the fire point below 300 °C. For SE3, Cargill gives no limit in the documentation available to us; the permissible residual quantity should be clarified beforehand.

Can every transformer be converted to natural ester?

According to Cargill, retrofilling with FR3 is typically possible up to 138 kV without internal modifications; above that, Cargill recommends a design review. Prerequisites are a verified condition, compatible gaskets and approval for bushings and tap changers. Transformers that previously contained silicone oil should not be filled with FR3.

Does the transformer have to be filled under vacuum when retrofilling?

Cargill prefers filling under vacuum with filtered fluid at a temperature of at least 50 °C and gives 60–65 °C at typically below 100 Pa for degassing. According to Cargill, atmospheric filling is typically only acceptable up to 69 kV. For small distribution transformers up to 25 kV, Cargill describes an atmospheric procedure directly from an IBC or drum.

Is a free-breathing transformer suitable for retrofilling with ester?

With FR3, according to Cargill, only if a system limits the air exchange above the fluid. Cargill describes the synthetic ester SE3 as suitable for free-breathing transformers. Cargill makes no statement on this for FR3r.

When are checks carried out after retrofilling?

Cargill provides for a sample before the conversion, another after filling and before energising, and a check sample after six months. On the day after energising, the temperature and pressure are checked, after which the tank pressure is recorded regularly.

Does Vielhauer carry out the retrofill on site?

No. The work on the transformer is carried out by your service partner or your maintenance team. We support the project with analyses in our own laboratory, material compatibility and miscibility tests, delivery of the ester fluid and the check after conversion.

More on this topic

Sources: Cargill: FR3 Fluid Retrofilling Power Class Transformers Guide (R2040, ©2020) · Cargill: FR3 Fluid Atmospheric Retrofilling Guide, Distribution Class (R2010/G2010) · Cargill: FR3 fluid retrofill brochure (©2024) · Cargill: Retrofilling (FR3 application page) · Cargill: FR3 Fluid Storage and Handling Guide (S10, 8/2020) · Cargill: Transformer power factor and FR3 fluid (R2100, 8/2020) · Cargill: Envirotemp FR3 Fluid R2000 (10/2016) · Cargill: SE3 Brochure (©2026) · IEC 62975:2021 – preview (introduction, table of contents) · IEC 61203:2025 – preview, VDE Verlag (introduction, table of contents) · AwSV § 13 – facilities with floating liquid substances (in German) · mv-lub.de: Topping up and mixing transformer oil

FR3™, FR3r™ and SE3™ are trademarks of Cargill, Incorporated; Shell MIDEL is a trademark of Shell Brands International AG. The trademarks are used here solely to identify the original products. Vielhauer GmbH is an independent dealer. All technical data are typical values from the manufacturers’ documentation and standards (as of 11/2026) and do not constitute a specification; the current data sheet applies in each case.