Standards for ester fluids: IEC 62770, IEC 61099 and other regulations

Which standards apply to ester fluids? IEC 62770 covers new natural esters and IEC 61099 new synthetic esters; in addition, there are maintenance standards, IEEE and ASTM standards and the classification under IEC 61039 – with an overview of the German versions.

Standards for ester fluids at a glance: from IEC 62770 to IEEE C57.147

For ester fluids in transformers, there is not a single standard but several sets of rules with separate tasks. The best known is IEC 62770 for new natural esters. It makes sense to divide them into three groups:

  • As-delivered condition: requirements for new, unused fluid – IEC 62770 for natural esters, IEC 61099 for synthetic esters and ASTM D6871 as the US specification for natural esters.
  • Operation and maintenance: tests, limits and actions for fluid in the equipment – IEC 62975, IEC 61203, IEEE C57.147 and, for gas analysis, IEEE C57.155.
  • Classification and application: the classification under IEC 61039 (including K-class) and IEC 60076-14 for transformers with high-temperature insulation materials.

The standards for mineral insulating oil – IEC 60296 for new oil and IEC 60422 for oil in service – are not intended for esters. You will find background information in our guide to IEC 60296.

StandardSubjectapplies toGerman version
IEC 62770:2024Specification and test methods for unused natural estersnew natural estersDIN EN IEC 62770 (VDE 0370-70):2025-05
IEC 61099:2010Requirements for unused synthetic organic estersnew synthetic estersDIN EN 61099 (VDE 0375-1):2011-06
ASTM D6871-26Specification for natural (vegetable oil) ester fluidsnew natural esters as received– (US standard)
IEC 62975:2021Guidelines for maintenance and use of natural estersnatural esters in serviceno DIN EN version identified
IEC 61203:2025Guidelines for maintenance and use of synthetic esterssynthetic esters in serviceDIN EN IEC 61203 (VDE 0375-2):2026-10
IEEE C57.147-2018Guide for acceptance and maintenance of natural estersnatural esters, receipt of goods and service– (IEEE)
IEEE C57.155-2014Interpretation of dissolved gases (DGA)Transformers with natural and synthetic esters– (IEEE)
IEC 61039:2025Classification of insulating liquidsall insulating liquidsDIN EN IEC 61039 (VDE 0389-1):2025-11
IEC 60076-14:2013liquid-immersed power transformers with high-temperature insulation materialsTransformersDIN EN 60076-14 (VDE 0532-76-14):2014-08

Editions as of November 2026, according to the IEC Webstore, DIN Media, ASTM and IEEE.

IEC 62770: new natural esters

IEC 62770 specifies the requirements and test methods for new, unused natural esters that insulate and cool in transformers and similar liquid-filled equipment. According to the standard, natural esters are triglycerides from vegetable oils or other biological feedstocks. Not covered are reclaimed esters, mixtures with other insulating liquids and low-viscosity ester-based liquids, for which IEC 63012 applies.

The second edition IEC 62770:2024 has applied since October 2024. The German version DIN EN IEC 62770 (VDE 0370-70):2025-05 replaces DIN EN 62770:2014-10. According to DIN Media, the changes include explanations of low-temperature behaviour and a modified determination of flash and fire point: both are now only measured in the Cleveland open cup. Because of their sensitivity to oxidation, the standard envisages natural esters for equipment that is not open to the atmosphere, such as hermetically sealed transformers or conservators with protection against contact with air.

IEC 61099: new synthetic esters

IEC 61099 describes requirements and test methods for unused synthetic organic esters used as an insulating and heat transfer medium in transformers, switchgear and similar equipment. This refers to esters made from fatty acids and polyols that contain only carbon, hydrogen and oxygen. The valid edition is IEC 61099:2010, in Germany DIN EN 61099 (VDE 0375-1):2011-06. DIN has been running a project for a new version, DIN EN IEC 61099, since December 2024.

The requirements differ noticeably from IEC 62770: IEC 61099 requires, for example, a pour point of no more than −45 °C and a test duration of 164 hours for the oxidation test to IEC 61125. You will find the values of Cargill SE3 compared with the limits on our page Cargill SE3.

ASTM D6871 and IEEE C57.147: the North American standards

ASTM D6871 is the US specification for high-fire-point natural ester fluids based on vegetable oil. According to ASTM, it only applies to new fluid as received, before any processing. The current version is D6871-26 (as of July 2026).

IEEE C57.147-2018 is a guide: it helps manufacturers and service companies evaluate unused natural esters on receipt and gives operators guidance on how to assess the fluid in service and keep it in serviceable condition. In Cargill’s FR3 documentation, ASTM D6871 and IEEE C57.147 are listed alongside IEC 62770.

Operation and maintenance: IEC 62975, IEC 61203 and IEEE C57.155

IEC 62975:2021 contains procedures and guidelines for the use and maintenance of natural esters in hermetically sealed transformers and other equipment. It applies to esters originally supplied to IEC 62770 or other standards such as ASTM D6871, and covers recommended tests, limits for esters in service, conditioning procedures and guidance on dissolved gas analysis and retrofilling. We have not found a German DIN EN version; a German draft standard (VDE 0370-19:2019-02) was withdrawn.

IEC 61203:2025 is the counterpart for synthetic esters: procedures and monitoring for use and maintenance, recommended tests and conditioning methods. The second edition was published in May 2025; the German version DIN EN IEC 61203 (VDE 0375-2):2026-10 replaces DIN EN 61203:1995-06.

IEEE C57.155-2014 deals with the interpretation of dissolved gases in transformers with natural and synthetic esters: gas generation, interpretation of results and recommended actions. IEEE has listed the guide as “Inactive-Reserved” since 27 March 2025. For mineral oil, IEC 60599 applies (see Oil analysis for transformer oil); you can read more about the analysis of esters in service in Oil analysis for ester fluids.

IEC 61039 and IEC 60076-14: classification and high temperature

IEC 61039 classifies insulating liquids. The current version is the third edition of 2025, in Germany DIN EN IEC 61039 (VDE 0389-1):2025-11, which replaces DIN EN 61039:2009-07. Best known is the classification by fire point: K-class means a fire point above 300 °C. What this means for installation and insurance is explained on our page Fire safety for ester-filled transformers.

IEC 60076-14:2013 applies to liquid-immersed power transformers with high-temperature insulation materials operated above the usual temperature limits, including converter, wind turbine and arc furnace transformers. Cargill refers to this standard and to IEEE C57.154 when it states a top-oil temperature of up to 140 °C for FR3 with thermally upgraded paper.

Which standards do Cargill FR3, FR3r and SE3 meet?

ProductTypeStandards according to Cargillfurther information according to Cargill
FR3natural ester (soybean oil)IEC 62770, IEEE C57.147, ASTM D6871K-class; FM Global approved, UL classified; high-temperature operation with reference to IEC 60076-14 and IEEE C57.154
FR3rnatural ester (rapeseed oil)IEC 62770, IEEE C57.147K-class, fire point 360 °C; FM Global and UL according to the product page
SE3synthetic esterIEC 61099K-class, fire point above 300 °C; suitable for free-breathing transformers according to Cargill

Cargill does not always state in its documentation which edition of a standard a statement refers to. For IEC 62770, this has been relevant since the 2024 edition, because the test method for the flash point, among other things, has changed. The IEC standards apply regardless of manufacturer, i.e. also to other esters such as those of the Shell MIDEL range, which we offer via mv-lub.eu (in German).

Using standards correctly in tenders and goods inwards

  • State the edition: “IEC 62770:2024” instead of just “IEC 62770” – otherwise it remains unclear which limits and test methods apply.
  • Separate as-delivered condition and service: limits for new fluid to IEC 62770 or IEC 61099 are not limits for fluid in service; IEC 62975 and IEC 61203 apply to that.
  • Specify natural or synthetic: for free-breathing transformers, Cargill names the synthetic ester SE3; IEC 62770 envisages natural esters for equipment without open access to air.
  • Request documentation: current technical data sheet and safety data sheet stating the standards and test methods.

We supply Cargill FR3, FR3r and SE3 across Europe with our own logistics, from 1-litre containers to bulk by road tanker, and test ester fluids in our own laboratory with oil analyses, miscibility analyses and material compatibility tests. We offer free qualification programmes for your equipment. Technical data sheets and safety data sheets are available on request – more in Buy ester fluids.

Ester fluids from Vielhauer GmbH

  • Delivery across Europe with our own logistics – 1 l, 8 l, 20 l, 25 l, drums (200 l), IBCs (1,000 l) and bulk by road tanker; availability and lead time on request
  • Our own laboratory for ester fluids: oil analyses, miscibility analyses and material compatibility tests
  • Retrofilling support from sampling through to the check after conversion
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request
  • Pack sizes, delivery and how to order: Buy FR3, FR3r and SE3

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Frequently asked questions

Which standard applies to natural esters?

IEC 62770 applies to new natural esters, currently in the 2024 edition, in Germany DIN EN IEC 62770 (VDE 0370-70):2025-05. In North America, ASTM D6871 is the corresponding specification. For natural esters in service, IEC 62975 provides guidelines on tests, limits and conditioning.

Which standard applies to synthetic esters?

New synthetic organic esters are specified to IEC 61099:2010, in Germany DIN EN 61099 (VDE 0375-1):2011-06. For synthetic esters in service, IEC 61203:2025 applies, German version DIN EN IEC 61203 (VDE 0375-2):2026-10.

What is the difference between IEC 62770 and IEC 62975?

IEC 62770 describes the requirements for new, unused natural esters as delivered. IEC 62975 is a guide for natural esters in service: tests, limits for used fluid and conditioning procedures.

Which standards does Cargill FR3 meet?

According to Cargill, FR3 meets IEC 62770, IEEE C57.147 and ASTM D6871 and is a K-class fluid. Cargill also states approval by FM Global and classification by UL. For high-temperature operation, Cargill refers to IEC 60076-14 and IEEE C57.154.

Does IEC 60422 also apply to ester fluids?

No. IEC 60422 is the guide for mineral insulating oils in service. For natural esters, IEC 62975 serves this purpose, and IEC 61203 for synthetic esters.

What changed with IEC 62770:2024?

According to DIN Media, flash and fire point are now only determined in the Cleveland open cup, and there are new explanations of low-temperature behaviour. For low-viscosity ester-based liquids, the standard refers to IEC 63012. The German version DIN EN IEC 62770 (VDE 0370-70) was published in May 2025.

More on this topic

Sources: iTeh: EN IEC 62770:2024 (edition 2.0, scope) · DIN Media: DIN EN IEC 62770 (VDE 0370-70):2025-05 · IEC Webstore: IEC 61099:2010 · DIN Media: DIN EN 61099 (VDE 0375-1):2011-06 · DIN: project DIN EN IEC 61099 (started 2024-12-11) · VDE Verlag: preview IEC 62975:2021 · DIN Media: draft DIN EN 62975 (VDE 0370-19):2019-02, withdrawn · IEC Webstore: IEC 61203:2025 · DIN Media: DIN EN IEC 61203 (VDE 0375-2):2026-10 · ASTM: D6871-26 · IEEE: C57.147-2018 · IEEE: C57.155-2014 (Inactive-Reserved) · DIN Media: DIN EN IEC 61039 (VDE 0389-1):2025-11 · VDE Verlag: preview IEC 61039:2025 · IEC Webstore: IEC 60076-14:2013 · DIN Media: DIN EN 60076-14 (VDE 0532-76-14):2014-08 · Cargill: FR3 fluid technical details · Cargill: FR3r fluid · Cargill: SE3 fluid · mv-lub.de: Oil analysis (IEC 60422, IEC 60599)

FR3™, FR3r™ and SE3™ are trademarks of Cargill, Incorporated; Shell MIDEL is a trademark of Shell Brands International AG. The trademarks are used here solely to identify the original products. Vielhauer GmbH is an independent dealer. All technical data are typical values from the manufacturers’ documentation and standards (as of 11/2026) and do not constitute a specification; the current data sheet applies in each case.