What the standard requires of mineral transformer oil, what distinguishes Type A from Type B and what has changed compared with the 2012 edition.
IEC 60296 specifies the properties a mineral insulating oil must have as delivered. The 5th edition was published in 2020 and in Germany applies as DIN EN IEC 60296 (VDE 0370-1):2022-12. It replaces the 2012 edition, which is still cited in many data sheets, maintenance plans and tenders.
The 2020 edition describes an oil by four characteristics, which together form the designation code:
| Characteristic | Code | Meaning |
|---|---|---|
| Application class | T / S | Transformer oil / low-temperature switchgear oil for outdoor switchgear in very cold climates |
| Origin | V / R | virgin / recycled, i.e. re-refined off-site or reclaimed |
| Performance group | A / B | High-grade oil / standard-grade oil |
| Antioxidant | I / T / U | inhibited (0.08–0.40 %) / trace-inhibited (≥ 0.01 to < 0.08 %) / uninhibited (not detectable) |
A virgin, fully inhibited high-grade transformer oil such as Shell Diala S4 ZX-I is therefore an oil of category T, V, A, I. Phenolic inhibitors such as DBPC count as antioxidants; Type A is always fully inhibited.
The oxidation test to IEC 61125 artificially ages the oil at 120 °C with a copper catalyst. Acidity, sludge and dissipation factor are then measured:
| Group | Test duration | Acidity | Sludge | DDF at 90 °C |
|---|---|---|---|---|
| Type A, inhibited | 500 h | max. 0.3 mg KOH/g | max. 0.05 % | max. 0.050 |
| Type B, inhibited | 500 h | max. 1.2 mg KOH/g | max. 0.8 % | max. 0.500 |
| Type B, trace-inhibited | 332 h | max. 1.2 mg KOH/g | max. 0.8 % | max. 0.500 |
| Type B, uninhibited | 164 h | max. 1.2 mg KOH/g | max. 0.8 % | max. 0.500 |
| Property | Test method | Requirement for transformer oil |
|---|---|---|
| Density at 20 °C | ISO 3675 | max. 895 kg/m³ |
| Viscosity at 40 °C | ISO 3104 | max. 12 mm²/s |
| Viscosity at LCSET (standard −30 °C) | ISO 3104 | max. 1,800 mm²/s |
| Pour point | ISO 3016 | at least 10 K below LCSET, standard max. −40 °C |
| Flash point (Pensky-Martens) | ISO 2719 | min. 135 °C |
| Neutralization value (acidity) | IEC 62021-1 | max. 0.01 mg KOH/g |
| Water content | IEC 60814 | max. 30 mg/kg; max. 40 mg/kg when delivered in drums and IBCs |
| Breakdown voltage | IEC 60156 | min. 30 kV as delivered; min. 70 kV after laboratory treatment |
| Dielectric dissipation factor (DDF) at 90 °C | IEC 60247 | max. 0.005 |
| Corrosive sulphur | DIN 51353 / IEC 62535 | non-corrosive |
| DBDS | IEC 62697-1 | not detectable (< 5 mg/kg) |
| Furanic compounds | IEC 61198 | not detectable for each compound (< 0.05 mg/kg) |
| PCB | IEC 61619 | not detectable (< 2 mg/kg) |
| Polycyclic aromatics (PCA) | IP 346 | max. 3 % |
State the full class in your enquiry and order – for example “IEC 60296:2020, transformer oil, Type A, inhibited” – and, if available, the approval or manufacturer list for your transformer. Check in the data sheet which edition of the standard the manufacturer refers to. With every delivery we send you the current data sheet and, on request, a certificate of analysis.
Transformer oil from Vielhauer GmbH
Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.
Type A is a fully inhibited high-grade oil with stricter requirements, above all for oxidation stability (500 h, acidity max. 0.3 mg KOH/g, sludge max. 0.05 %), colour, interfacial tension, sulphur content and stray gassing. Type B is the standard-grade oil; it can be uninhibited, trace-inhibited or inhibited and has wider limits (acidity max. 1.2 mg KOH/g, sludge max. 0.8 %).
LCSET stands for lowest cold start energizing temperature – the lowest temperature at which a transformer may be energized from cold. Unless otherwise specified, −30 °C applies. The requirements for viscosity (max. 1,800 mm²/s at −30 °C) and pour point (at least 10 K below the LCSET, i.e. max. −40 °C) are derived from it.
Yes. Since the 2020 edition, IEC 60296 applies to virgin oils and to recycled oils that have been re-refined off-site or reclaimed. The origin is indicated in the designation code with V (virgin) or R (recycled).
DIN EN IEC 60296 (VDE 0370-1):2022-12. It replaces DIN EN 60296 (VDE 0370-1):2012-12. In other EU countries, IEC 60296 is published as EN IEC 60296 by the national standards bodies.
Shell, Diala and Shell MIDEL are trademarks of Shell Brands International AG. They are used here solely to identify the original products. Vielhauer GmbH sells Shell Diala products as an independent dealer. TotalEnergies and ISOVOLTINE are trademarks of TotalEnergies SE. All technical data are typical values from the manufacturers’ data sheets (as of October 2026) and do not constitute a specification; the current data sheet applies.