Mineral oil or ester in the transformer? A technical comparison

Fire point, moisture tolerance, viscosity and limits of use: what distinguishes mineral transformer oil from ester fluids and when each solution makes sense.

For oil-filled transformers there are now two large families of insulating liquids to choose from: proven mineral oil to IEC 60296 and ester fluids – synthetic esters to IEC 61099 and natural esters to IEC 62770. As a supplier of both families, we compare them here on purely technical grounds.

The main differences

CharacteristicMineral oilSynthetic esterNatural ester
StandardIEC 60296IEC 61099IEC 62770
Fire class (IEC 61039)O (fire point ≤ 300 °C)K (fire point > 300 °C)K (fire point > 300 °C)
Typical flash/fire pointapprox. 150 / 170 °C; Shell Diala S4 ZX-I: flash point 191 °Capprox. 260 / 316 °Capprox. 316 / 360 °C
Viscosity at 40 °Cbelow 12 mm²/s (S4 ZX-I: 9.8)approx. 29 mm²/sapprox. 32–37 mm²/s
Pour pointbelow −40 °Cbelow −45 °Chigher than for mineral oil, depending on the product about −10 to −30 °C
Water saturation at 20 °Capprox. 55 ppmapprox. 2,600 ppmapprox. 1,100 ppm
Use in free-breathing transformersyesyesonly hermetically sealed or with membrane

Typical values from technical literature (including the University of Stuttgart and CIGRE) and manufacturers’ data; individual products differ.

What the differences mean in practice

Fire safety

Mineral oils belong to class O, esters with a fire point above 300 °C to class K (“less flammable”). Where transformers are installed in buildings, tunnels, wind turbines or densely built-up areas, fire safety regulations or insurers often require class K fluids.

Moisture

Esters dissolve many times more water. Absolute water limits for mineral oil therefore cannot be applied to esters – what matters is the relative saturation. Separate guidelines apply to the assessment of ester samples, for example IEC 62975 for natural esters.

Cooling and low temperatures

Mineral oil is considerably less viscous and transfers heat better for the same design. Esters may require additional cooling ducts. At very low temperatures, mineral oils and synthetic esters have advantages over natural esters.

Experience and approvals

Mineral oil is the standard solution proven over decades, with the most manufacturer approvals and the lowest price per litre. Esters have long been used in special transformers (rail, wind) and increasingly in distribution and power transformers.

Which oil when?

  • Mineral oil – if the manufacturer provides for it, there are no special fire safety requirements and cooling and low-temperature behaviour are the priority. Our recommendation: Shell Diala S4 ZX-I.
  • Ester – if class K is required, for installation in buildings or sensitive environments, or if high moisture tolerance is desired. We compare Cargill’s ester fluids (FR3, FR3r, SE3) in Ester fluids for transformers; Shell MIDEL ester fluids can be found at mv-lub.eu.

Retrofilling: from mineral oil to ester

An existing mineral oil transformer can be converted to ester. Residual mineral oil has to be minimised and the compatibility of all materials checked – more in Topping up and mixing and at mv-lub.eu/retrofilling. We support you with material compatibility tests and analyses in our own laboratory.

Transformer oil from Vielhauer GmbH

  • Delivery across Europe with our own logistics – in 20 l cans, 209 l drums, 1,000 l IBCs and by road tanker
  • Short lead times: usually 2 to 4 working days
  • Oil analyses in our own laboratory, plus miscibility analyses and material compatibility tests
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Frequently asked questions

Can a mineral oil transformer be converted to ester fluid?

Yes, this is called retrofilling. The mineral oil is removed as far as possible, because residues lower the fire point of the ester fluid, and bushings, tap-changers and gaskets are checked for compatibility. Because of the higher viscosity of esters, cooling also has to be assessed.

Which fluid is suitable for transformers in buildings?

Where fire safety regulations or insurers require less flammable fluids, class K fluids to IEC 61039 are often used, i.e. with a fire point above 300 °C – these are esters and silicone oils. Mineral oils belong to class O. Which requirements apply is determined by local regulations and the operator.

Is ester fluid more expensive than mineral oil?

Per litre, usually yes. Depending on the project, this is offset by lower structural fire protection requirements and higher moisture tolerance. We advise you on both options.

More about transformer oil

Shell, Diala and Shell MIDEL are trademarks of Shell Brands International AG. They are used here solely to identify the original products. Vielhauer GmbH sells Shell Diala products as an independent dealer. TotalEnergies and ISOVOLTINE are trademarks of TotalEnergies SE. All technical data are typical values from the manufacturers’ data sheets (as of October 2026) and do not constitute a specification; the current data sheet applies.