Transformer oil (insulating oil): Shell Diala, testing and supply

Mineral transformer oil to IEC 60296 – from 20 l cans to road tankers, delivered across Europe usually within 2 to 4 working days, with oil analyses in our own laboratory.

What transformer oil has to do

Transformer oil – also called insulating oil – has three jobs in a transformer. Together with the paper, it insulates the windings from each other and from the tank; it cools by carrying the loss heat to the radiators; and it carries information: dissolved gases, water, acids and paper degradation products in the oil show how the transformer is doing. That is why it is not only a question of the right oil, but also of filling it dry, clean and degassed and testing it regularly afterwards.

The standard: IEC 60296:2020

Mineral insulating oils for transformers and switchgear are purchased to IEC 60296 – in Germany published as DIN EN IEC 60296 (VDE 0370-1):2022-12. The current 5th edition of 2020 distinguishes by performance:

GroupInhibitor (DBPC)Oxidation test IEC 61125Classification
Type A, inhibited (I)0,08–0,40 %500 h, stricter limitsHigh-grade oil; corresponds to the former 2012 edition, Table 2 with clause 7.1
Type B, inhibited (I)0,08–0,40 %500 hStandard oil
Type B, trace-inhibited (T)≥ 0.01 to < 0.08 %332 hStandard oil
Type B, uninhibited (U)not detectable164 hStandard oil

Requirements for all oils include: non-corrosive to copper and silver, no detectable DBDS or PCB, a flash point of at least 135 °C and a breakdown voltage of at least 70 kV after laboratory treatment. All limits, the designation code and the differences from the 2012 edition are explained in detail in IEC 60296:2020 explained.

GTL or naphthenic?

Conventional transformer oils are refined from naphthenic crude oils. The Shell Diala grades S4 ZX-I and S4 ZX-IG, by contrast, are based on GTL base oil (gas-to-liquids): it is produced from natural gas by Fischer-Tropsch synthesis and is practically sulphur-free – Shell states a sulphur content below the detection limit of 1 ppm. In service this means above all: no corrosive sulphur and no DBDS, without having to add a metal passivator. Both types of oil can meet IEC 60296; what matters is the class your transformer requires.

Corrosive sulphur and DBDS

At high temperatures, sulphur compounds in the oil can form copper sulphide, which deposits on conductors and in the paper and weakens the insulation. The best-known cause is DBDS (dibenzyl disulphide). IEC 60296 therefore requires three proofs: non-corrosive to DIN 51353 (silver strip), not potentially corrosive to IEC 62535 (copper with paper, 72 h at 150 °C) and DBDS not detectable to IEC 62697-1. How these tests are used in service is described in our guide Oil analysis and DGA.

Our range of transformer and insulating oils

ProductBaseStandardTypical applicationMore
Shell Diala S4 ZX-IGTL, fully inhibitedIEC 60296:2020 Type APower and distribution transformersProperties and supply
Shell Diala S4 ZX-IGGTL, inhibited, gas-absorbingIEC 60296:2020 Type A; ASTM D3487 Type IIInstrument transformers, bushings, high field strengthsProperties and supply
Shell Diala S5 BDGTL base oil with alkylbenzene, inhibitedIEC 60296:2020 Type A; ASTM D3487 Type IIPower and distribution transformers, very low temperaturesProperties and supply
Shell Diala Cable OilAlkylbenzeneIEC 60867 Class IOil-filled cables, capacitors, bushingsProperties and supply
TotalEnergies ISOVOLTINEmineralsee data sheetTransformersISOVOLTINE II · II X · P1 · P2

All Shell Diala grades with their properties side by side can be found in Shell Diala at a glance. If you are looking for an older product name such as Diala B, Diala DX or S3 ZX-I, the successors are listed in Shell Diala: old names and successors.

Delivery, laboratory and service

We don’t just supply transformer oil, we support you in using it: oil analyses in our own laboratory, miscibility analyses before topping up, material compatibility tests and free qualification programmes. We run our own logistics across Europe – from cans to road tankers.

Transformer oil from Vielhauer GmbH

  • Delivery across Europe with our own logistics – in 20 l cans, 209 l drums, 1,000 l IBCs and by road tanker
  • Short lead times: usually 2 to 4 working days
  • Oil analyses in our own laboratory, plus miscibility analyses and material compatibility tests
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Transformer oil guides

News on standards, manufacturers and regulations: News (in German). Ester fluids as an alternative to mineral oil: Cargill FR3, FR3r and SE3 compared.

Frequently asked questions

What is the difference between inhibited and uninhibited transformer oil?

Inhibited oil contains an oxidation inhibitor, usually DBPC (2,6-di-tert-butyl-p-cresol). IEC 60296:2020 requires 0.08 to 0.40 % of it. Uninhibited oil (U) contains no detectable antioxidant, trace-inhibited oil (T) less than 0.08 %. Inhibited oils are considerably more stable against oxidation but gradually consume their inhibitor in service. Which group belongs in your transformer is specified by the manufacturer or operator.

Which transformer oil is right for my transformer?

The decisive factors are the requirements of the transformer manufacturer and of your grid or plant operator: standard class to IEC 60296 (Type A or B), inhibited or uninhibited, and possibly an approval or manufacturer list. For existing equipment, the oil already in it also matters. Send us the rating plate, the oil designation or a sample – we will recommend the right oil and, if needed, check miscibility in our own laboratory.

Can I mix Shell Diala S4 ZX-I with other transformer oil?

Under IEC 60296:2020, mineral oils of the same class, type, group and LCSET and with the same types of additives are considered compatible in mixtures of up to 10 % without further testing. In all other cases – for example inhibited with uninhibited oil – the mixture has to be reclassified and tested. We carry out these miscibility analyses in our own laboratory.

In which pack sizes and how quickly do you deliver transformer oil?

We deliver in 20 l cans, 209 l drums, 1,000 l IBCs and in bulk by road tanker – across Europe with our own logistics. The lead time is usually 2 to 4 working days.

What water hazard class does transformer oil have?

That depends on the product and is stated in the safety data sheet. According to the German safety data sheets (August 2026), Shell Diala S4 ZX-I, S4 ZX-IG and S5 BD are classified as WGK 1 (German water hazard class: slightly hazardous to water).

Shell, Diala and Shell MIDEL are trademarks of Shell Brands International AG. They are used here solely to identify the original products. Vielhauer GmbH sells Shell Diala products as an independent dealer. TotalEnergies and ISOVOLTINE are trademarks of TotalEnergies SE. All technical data are typical values from the manufacturers’ data sheets (as of October 2026) and do not constitute a specification; the current data sheet applies.