Shell Diala S4 ZX-IG: gas-absorbing insulating oil for instrument transformers and bushings

Inhibited GTL insulating oil with negative gassing tendency to ASTM D3487 Type II and IEC 60296:2020 Type A – for high-voltage instrument transformers, bushings and high field strengths.

At a glance
Product typeinhibited, gas-absorbing premium insulating oil
Base oilGTL; only DBPC as antioxidant and a small proportion of aromatic hydrocarbons for gas absorption; free of PCB, DBDS and passivators
SpecificationASTM D3487 Type II; IEC 60296:2020 Type A (or IEC 60296:2012 Table 2 with clause 7.1)
ApplicationHigh-voltage instrument transformers, bushings, applications with high voltage gradients
Pack sizes209 l drum; other pack sizes on request
ClassificationWGK 1; H304, signal word “Danger”, GHS08 (per SDS 08/2026)

What Shell Diala S4 ZX-IG is designed for

In instrument transformers and bushings, the oil is exposed to very high electrical field strengths in a confined space. If partial discharges produce gases there, bubbles can form and further weaken the insulation. S4 ZX-IG therefore contains a small proportion of aromatic hydrocarbons in addition to the GTL base oil: they make the oil absorb gas under electrical stress instead of releasing it. The gassing tendency to IEC 60628 (method A) is typically −5 mm³/min.

Otherwise S4 ZX-IG behaves like S4 ZX-I: fully inhibited with 0.2 % DBPC, no corrosive sulphur, very low dissipation factor and good low-temperature properties. With typically 6 mg/kg water as delivered, it is particularly dry.

Typical properties

PropertyTest methodLimitTypical S4 ZX-IG
Density at 20 °CISO 3675max. 895 kg/m³ (IEC 60296)806 kg/m³
Viscosity at 40 °CISO 3104max. 12 mm²/s (IEC 60296)9.4 mm²/s
Viscosity at −30 °CISO 3104max. 1,800 mm²/s (IEC 60296)381 mm²/s
Viscosity at 100 °C / 0 °CASTM D445max. 3 / 76 mm²/s (ASTM D3487)2.7 / 58 mm²/s
Flash point (Pensky-Martens)ISO 2719min. 135 °C (IEC 60296)158 °C
Pour pointISO 3016max. −40 °C (IEC 60296)−42 °C
Neutralization value (acidity)IEC 62021-1max. 0.01 mg KOH/g0.01 mg KOH/g
Total sulphurASTM D5185max. 500 mg/kg1 mg/kg
Corrosive sulphurDIN 51353 / IEC 62535 / ASTM D1275Bnon-corrosivenon-corrosive
Breakdown voltage as delivered / after treatmentIEC 60156min. 30 / 70 kV59 / 75 kV
Impulse breakdown voltageASTM D3300min. 145 kV (ASTM D3487)288 kV
Dielectric dissipation factor (DDF) at 90 °CIEC 60247max. 0.0050,001
Interfacial tension at 25 °CASTM D971min. 40 mN/m (ASTM D3487)53 mN/m
Gassing tendencyIEC 60628 Ano requirement−5 mm³/min
Oxidation stability (rotating pressure vessel)ASTM D2112min. 195 min (ASTM D3487)650 min
Water content, drum/IBC and bulkIEC 60814max. 40 / 30 mg/kg6 mg/kg
Inhibitor (DBPC)IEC 606660,08–0,40 %0,2 %

Typical values according to the German Shell data sheet version 4.1 of 3 August 2026 (identical to English version 3.9). Typical values are not a specification.

S4 ZX-IG or S4 ZX-I?

S4 ZX-IS4 ZX-IG
Gassing behaviournot stated; “non-stray gassing” to IEC 60296gas-absorbing, −5 mm³/min (IEC 60628 A)
Flash point191 °C158 °C
Water content as delivered14 mg/kg (drum/IBC)6 mg/kg
StandardsIEC 60296:2020 Type AIEC 60296:2020 Type A; ASTM D3487 Type II
Main applicationPower and distribution transformersInstrument transformers, bushings

More about S4 ZX-I: Shell Diala S4 ZX-I. All grades compared: Shell Diala at a glance.

Ordering

Business customers can order the 209 l drum directly in our online shop (German-language). Other pack sizes and bulk deliveries are available on request.

Transformer oil from Vielhauer GmbH

  • Delivery across Europe with our own logistics – in 20 l cans, 209 l drums, 1,000 l IBCs and by road tanker
  • Short lead times: usually 2 to 4 working days
  • Oil analyses in our own laboratory, plus miscibility analyses and material compatibility tests
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Frequently asked questions

What does the negative gassing tendency of Shell Diala S4 ZX-IG mean?

The gassing tendency to IEC 60628 (method A) describes whether an oil releases or absorbs gas under electrical discharge. A negative value – typically −5 mm³/min for S4 ZX-IG – means that the oil absorbs gas. This is desirable in equipment with high field strengths such as instrument transformers and bushings, because no gas bubbles should form there.

When do I use S4 ZX-IG instead of S4 ZX-I?

When the manufacturer requires a gas-absorbing oil, typically for high-voltage instrument transformers, bushings and special applications with high voltage gradients. For power and distribution transformers, S4 ZX-I is the standard oil.

Which standards does Shell Diala S4 ZX-IG meet?

ASTM D3487 Type II and – according to the English and Austrian data sheets – IEC 60296 (edition 5, 2020) Type A. The German data sheet (version 4.1 of 3 August 2026) instead cites the previous edition IEC 60296:2012 Table 2 with clause 7.1, which corresponds to Type A.

Is S4 ZX-IG the successor to Diala GX or S3 ZX-IG?

Diala GX was renamed Diala S3 ZX-IG around 2011. In Shell’s 2015 product overview, S4 ZX-IG takes on the role of the gas-absorbing special oil; however, we have no explicit statement from Shell that it is the successor.

More about transformer oil

Shell, Diala and Shell MIDEL are trademarks of Shell Brands International AG. They are used here solely to identify the original products. Vielhauer GmbH sells Shell Diala products as an independent dealer. TotalEnergies and ISOVOLTINE are trademarks of TotalEnergies SE. All technical data are typical values from the manufacturers’ data sheets (as of October 2026) and do not constitute a specification; the current data sheet applies.