Fully inhibited GTL-based insulating oil to IEC 60296:2020 Type A for power and distribution transformers – available in cans, drums, IBCs and by road tanker, usually within 2 to 4 working days.
| At a glance | |
|---|---|
| Product type | Premium insulating oil (transformer oil), fully inhibited |
| Base oil | GTL (gas-to-liquids), sulphur content below 1 ppm; free of PCB, DBDS and passivators |
| Specification | IEC 60296:2020 Type A; IEC 60296:2012 Table 2 (I) with clause 7.1; GB 2536-2025 |
| Application | Power and distribution transformers, including heavily loaded applications |
| Pack sizes | 20 l can, 209 l drum, 1,000 l IBC, road tanker |
| Lead time | usually 2 to 4 working days, across Europe |
| Classification | WGK 1; H304, signal word “Danger”, GHS08 (per SDS 08/2026) |
| Predecessors | Shell Diala S2 ZU-I and S3 ZX-I (replaced in Q1 2015), before that Diala B and DX – all old names |
S4 ZX-I is made from GTL base oil, which Shell produces from natural gas by Fischer-Tropsch synthesis. According to the data sheet, the sulphur content is below the detection limit of 1 ppm (ASTM D5185). The oil is therefore inherently non-corrosive to copper – without a metal passivator and without other additives against copper corrosion. S4 ZX-I passes all corrosive sulphur tests required by IEC 60296 and contains no DBDS.
After the 500-hour oxidation test to IEC 61125, S4 ZX-I typically reaches an acidity of 0.02 mg KOH/g, 0.01 % sludge and a dissipation factor of 0.001 – the limits for Type A are 0.3 mg KOH/g, 0.05 % and 0.05. This is the basis for a long oil life, especially in heavily loaded transformers.
With a pour point of −45 °C and 438 mm²/s at −30 °C, the oil remains fluid even at low start-up temperatures and carries heat away reliably. At the standard lowest cold start energizing temperature (LCSET −30 °C), IEC 60296 allows up to 1,800 mm²/s.
Shell dries and handles S4 ZX-I so that it arrives with a low water content and high breakdown voltage: typically 14 mg/kg in drums and IBCs, 10 mg/kg in bulk. In the stray gassing test to IEC 60296, hydrogen, methane and ethane remain below 5 µl/l – Shell classifies the oil as “non-stray gassing”. This makes later dissolved gas analyses easier to interpret.
| Property | Test method | Limit IEC 60296 Type A | Typical S4 ZX-I |
|---|---|---|---|
| Density at 20 °C | ISO 3675 | max. 895 kg/m³ | 805 kg/m³ |
| Kinematic viscosity at 40 °C | ISO 3104 | max. 12 mm²/s | 9.8 mm²/s |
| Kinematic viscosity at −30 °C | ISO 3104 | max. 1,800 mm²/s | 438 mm²/s |
| Flash point (Pensky-Martens) | ISO 2719 | min. 135 °C | 191 °C |
| Pour point | ISO 3016 | max. −40 °C | −45 °C |
| Neutralization value (acidity) | IEC 62021-1 | max. 0.01 mg KOH/g | < 0.01 mg KOH/g |
| Interfacial tension | IEC 62961 | min. 43 mN/m | 51 mN/m |
| Colour | ISO 2049 | max. L0.5 | L0.5 |
| Total sulphur | ISO 14596 | max. 0.05 % | < 0,001 % |
| Corrosive sulphur | DIN 51353 / IEC 62535 | non-corrosive | non-corrosive |
| DBDS | IEC 62697-1 | not detectable (< 5 mg/kg) | not detectable |
| Breakdown voltage as delivered | IEC 60156 | min. 30 kV | 50–60 kV |
| Breakdown voltage after treatment | IEC 60156 | min. 70 kV | 78 kV |
| Dielectric dissipation factor (DDF) at 90 °C | IEC 60247 | max. 0.005 | 0,001 |
| Oxidation 500 h/120 °C: acidity / sludge / DDF | IEC 61125 | max. 0.3 / 0.05 % / 0.05 | 0,02 / 0,01 % / 0,001 |
| Water content, drum/IBC | IEC 60814 | max. 40 mg/kg | 14 mg/kg |
| Water content, bulk | IEC 60814 | max. 30 mg/kg | 10 mg/kg |
| Inhibitor (DBPC) | IEC 60666 | 0,08–0,40 % | 0,2 % |
| PCB | IEC 61619 | not detectable (< 2 mg/kg) | not detectable |
| Stray gassing (H₂, CH₄, C₂H₆) | IEC 60296 Annex A | max. 50 µl/l each | ≤ 5 µl/l each |
Typical values according to Shell data sheet version 5.2 of 3 August 2026; the current German version (version 5.1 of 6 October 2025) states the same values. Typical values are not a specification.
According to the Shell data sheet, S4 ZX-I meets or is listed in the lists or specifications of, among others:
Whether an oil is approved for your specific transformer is confirmed, in case of doubt, by the manufacturer. We support you with data sheets, certificates of analysis and – on request – a free qualification programme.
In Germany, Shell discontinued the grades Diala S2 ZU-I (uninhibited) and Diala S3 ZX-I (inhibited) in the first quarter of 2015 and introduced S4 ZX-I as their common successor. Important when topping up older equipment: if you have been using uninhibited oil, adding S4 ZX-I means mixing two different groups under IEC 60296. Such a mixture has to be reclassified and tested – more in Topping up and mixing transformer oil.
| Pack sizes | Ordering |
|---|---|
| 20 l can | order in our online shop (German-language) |
| 209 l drum | order in our online shop (German-language) |
| 1,000 l IBC | on request |
| Road tanker (bulk) | on request, across Europe |
Transformer oil from Vielhauer GmbH
Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.
Yes, S4 ZX-I is fully inhibited. The data sheet states 0.2 % DBPC; IEC 60296:2020 requires 0.08 to 0.40 % for Type A.
IEC 60296 (edition 5, 2020) Type A, “fully inhibited high grade”, and under the previous edition IEC 60296:2012 Table 2 (inhibited) with clause 7.1 (higher oxidation stability and low sulphur content). Shell also lists the Chinese standard GB 2536-2025 and the specification ENGIE Laborelec LPS 05/2020.
Shell Diala S4 ZX-I. In Germany, Shell replaced both grades with S4 ZX-I in the first quarter of 2015. Please note: S2 ZU-I was uninhibited, S4 ZX-I is inhibited – before topping up equipment that contains uninhibited oil, the mixture should be tested and the manufacturer or operator consulted.
Shell describes its GTL oils as fully miscible with conventional insulating oils. Under IEC 60296:2020, however, only the following applies without further testing: same class, type, group and LCSET and the same types of additives, up to 10 %. Beyond that, we recommend a miscibility analysis – which we carry out in our own laboratory.
Shell delivers S4 ZX-I dried (typically 14 mg/kg water in drums and IBCs, 10 mg/kg in bulk). Whether additional drying and degassing is needed before filling depends on the equipment and the manufacturer’s requirements. For high-voltage transformers, a water content of no more than 10 mg/kg after filling is often required.
The current Shell data sheet (version 5.2 of 3 August 2026) relates the statement “readily biodegradable according to the test criteria of OECD 301” exclusively to the base oil used. The German safety data sheet contains no corresponding classification of the finished product. Older data sheet versions from 2025 still worded this differently.
WGK 1 (German water hazard class: slightly hazardous to water) according to the German safety data sheet of 3 August 2026.
Shell, Diala and Shell MIDEL are trademarks of Shell Brands International AG. They are used here solely to identify the original products. Vielhauer GmbH sells Shell Diala products as an independent dealer. TotalEnergies and ISOVOLTINE are trademarks of TotalEnergies SE. All technical data are typical values from the manufacturers’ data sheets (as of October 2026) and do not constitute a specification; the current data sheet applies.