Ester-filled transformers for wind power, solar parks and battery storage

An ester-filled transformer in a wind turbine, solar park or battery storage system offers K-class fire safety and high moisture tolerance; whether Cargill FR3, FR3r or SE3 is right depends mainly on the cold at the site and the transformer design.

Ester-filled transformers in wind power, solar parks and battery storage

Transformers in renewable energy installations operate under conditions that a grid transformer rarely sees: in the nacelle or tower of a wind turbine, in compact substations and skids in solar parks, next to battery containers, often difficult to access and sometimes close to water. An ester-filled transformer in a wind turbine, solar park or battery storage system should therefore deliver three things above all: a low fire load, high moisture tolerance and a compact design. Which ester fluid is right depends mainly on the climate and the transformer design.

Requirements by application

Wind power: nacelle, tower and tower base

Step-up transformers for wind turbine generators are covered by IEC/IEEE 60076-16 (edition 2.0, 2018). It covers dry-type and liquid-immersed transformers with a highest voltage for equipment of up to 72.5 kV. Among other things, the standard deals with installation in the tower or nacelle, humidity and salinity of the environment, vibration, harmonics, temperature cycling and – for the tower and nacelle – flammability; a fire behaviour test is provided as a special test. For high-temperature insulation systems, it refers to IEC 60076-14.

According to the information sheet on wind turbines issued by the German Federal/State Working Group on Handling Substances Hazardous to Water (BLAK UmwS, as of 16 May 2023), transformers can be located in a substation outside the tower, at the tower base, in the tower or in the nacelle; they contain up to around 3,000 l of insulating liquid. According to the information sheet, almost all new installations use floating insulating liquids classified as generally hazardous to water (awg) under the German AwSV.

For FR3 in wind turbines, Cargill mainly highlights the compact, lightweight design and fire safety (K-class). According to Cargill, with thermally upgraded paper (TUK) and FR3, a transformer can be rated in thermal class 140 and operated at a hot-spot temperature of 130 °C. For offshore installations, Cargill points out that dry-type transformers to IEC 60076-11 should not be used at ambient humidity above 92 %.

Solar parks: compact substations and skids

In a solar park, the load fluctuates with solar irradiance, inverters generate harmonics, and the transformers sit in confined spaces in substations or skids. Cargill states that FR3 absorbs more than ten times as much dissolved water as mineral oil and allows up to 20 % more loading capability than mineral oil, possibly more in transformers designed for FR3.

Documented examples from Cargill case studies:

  • Enel Green Power, Spain: in the VIDCO solar cluster in Extremadura (136 MW), 21 transformers filled with FR3 were installed, designed for higher operating temperatures and greater power density; one example is a unit with 5,000 kVA rated power and 7,000 kVA peak power in a solar skid. According to the case study, the project saved almost 14 t of iron, aluminium and insulating paper; commissioning took place at the end of 2022.
  • Sprng Energy, India: in the 125 MW Sprng Ujjvala project, two 66/33 kV transformers rated 52.5/63 MVA and ten 33/0.63 kV inverter transformers have been operating with FR3 since December 2022. The case study gives the fluctuating load, heat and harmonics at the inverter and fire safety as the reasons; the large transformers were installed without a nitrogen injection fire protection system (NIPS).
  • NTPC, India: dry-type transformers were originally planned for the Ramagundam floating PV plant (100 MW). According to Cargill, they were replaced by lighter FR3-filled units; by January 2022, 20 of 40 planned transformers had been installed.

Battery energy storage systems (BESS)

For battery storage, fire safety is the top priority. According to Cargill, cell failures are the main cause of BESS fires; the transformer should therefore not add any extra fire load. For FR3, Cargill cites twice the fire point of mineral oil, up to 20 % more loading capability for non-free-breathing transformers and further reserves with TUK paper or a design optimised for FR3. According to Cargill, FM Global recognises FR3 for most installations as a safeguard equivalent to clearances, fire walls and fire suppression systems. More in Fire safety with ester fluids.

Cold, moisture, air ingress: FR3, FR3r or SE3?

Two questions are decisive when choosing between the three Cargill fluids: how cold does it get at the site, and is the transformer hermetically sealed or free-breathing?

  • Cold: according to Cargill, the pour point (ISO 3016) is −21 °C for FR3, −33 °C for FR3r and below −50 °C for SE3. For FR3, Cargill states dielectric properties down to −50 °C and normal operation down to −25 °C according to IEC; for cold starts, Cargill recommends preheating the top oil to −10 to 0 °C and blocking tap changers at oil temperatures below −10 °C.
  • Air ingress: natural esters oxidise with atmospheric oxygen. Cargill recommends FR3 for hermetically sealed transformers or units with limited air ingress; IEC 62770 envisages natural esters for hermetically sealed equipment or conservators with a membrane. According to Cargill, SE3 is suitable for free-breathing transformers.
  • Moisture: esters dissolve considerably more water than mineral oil – at 20 °C approx. 1,100 ppm (natural ester) and approx. 2,600 ppm (synthetic ester) respectively, compared with approx. 55 ppm. This relieves the paper insulation in humid environments.
ApplicationTypical requirementSuitable fluid
Nacelle or tower transformer, hermetically sealedFire safety in the tower, compact design, vibration, humidityFR3 or FR3r
Wind turbine in a cold regionCold start, fluidity at low temperaturesFR3r (pour point −33 °C); SE3 for free-breathing designs or extreme cold
Offshore and coastal sitesHumidity and salt (IEC 60076-16), difficult accessFR3 or FR3r hermetically sealed; SE3 if free-breathing
Solar compact substation, skid, inverter transformerFluctuating load, load peaks, spaceFR3 or FR3r, hermetically sealed
Floating PV, site close to waterWeight, water protection under the German AwSVFR3 or FR3r; note the awg classification
Battery storageNo additional fire load, cyclic load, clearancesFR3 or FR3r, hermetically sealed; SE3 if free-breathing
Grid connection substation with open conservatorFluid in contact with airSE3, or FR3 with limited air ingress

The table is for guidance only. The manufacturer determines which fluid a transformer receives as part of the design. You will find a comparison of properties in Ester fluids: FR3, FR3r and SE3; in addition to Cargill, we also supply the ester fluids from Shell MIDEL (website in German).

Water protection: understanding the AwSV and awg correctly

Natural esters such as FR3 and FR3r consist mainly of vegetable oil. The German Environment Agency (Umweltbundesamt) has officially published liquid vegetable triglycerides as floating substances (Kenn-Nr. 9442); under the AwSV (German Ordinance on Facilities for Handling Substances Hazardous to Water), they are considered generally hazardous to water (awg), not as non-hazardous to water. For SE3, we will provide the classification on request.

  • Under § 39(11) AwSV, facilities with awg substances are not assigned a hazard level.
  • Under § 13(1) AwSV, the facility requirements for floating substances apply if entry into surface waters cannot be ruled out – this must be checked for floating PV or sites close to water.
  • For insulating liquid in wind turbines, the BLAK information sheet requires a liquid-tight containment facility.

In its data sheet, Cargill states that FR3 is readily biodegradable to OECD 301 B. This does not change the awg classification. Details in Disposal, AwSV and WGK (Germany).

What this means for operators and manufacturers

For wind farms, solar parks and storage systems, what matters is that the right fluid is on site in the right quantity at the right time – for the initial filling at the manufacturer as well as for topping up in service. As an independent dealer, Vielhauer GmbH supplies Cargill FR3, FR3r and SE3 across Europe with its own logistics, in 1 l, 8 l, 20 l and 25 l containers for service and topping up through to 200 l drums, 1,000 l IBCs and bulk by road tanker; availability and lead time on request.

In our own laboratory, we analyse ester samples, test miscibility and material compatibility, and support the conversion of existing mineral oil transformers by retrofilling from sampling through to the check afterwards. We offer free qualification programmes and will send you data sheets and safety data sheets. Please send questions about your project via our contact form.

Ester fluids from Vielhauer GmbH

  • Delivery across Europe with our own logistics – 1 l, 8 l, 20 l, 25 l, drums (200 l), IBCs (1,000 l) and bulk by road tanker; availability and lead time on request
  • Our own laboratory for ester fluids: oil analyses, miscibility analyses and material compatibility tests
  • Retrofilling support from sampling through to the check after conversion
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request
  • Pack sizes, delivery and how to order: Buy FR3, FR3r and SE3

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Frequently asked questions

Why are ester-filled transformers used in wind power?

In the nacelle and tower, fire safety, compact design and moisture tolerance are what count. With a fire point above 300 °C, ester fluids such as FR3, FR3r and SE3 are K-class. According to the BLAK information sheet on wind turbines (2023), almost all new installations use floating insulating liquids classified as awg (generally hazardous to water under the German AwSV).

Which standard applies to transformers in wind turbines?

IEC/IEEE 60076-16 (edition 2.0, 2018) applies to dry-type and liquid-immersed step-up transformers for wind turbine generators up to 72.5 kV. Among other things, it covers installation in the tower and nacelle, humidity, salt, vibration and flammability. For high-temperature insulation, it refers to IEC 60076-14.

FR3, FR3r or SE3 – which is right for cold conditions?

According to Cargill, the pour point is −21 °C (FR3), −33 °C (FR3r) and below −50 °C (SE3). FR3r is therefore the natural ester option for colder sites. For extreme cold or free-breathing transformers, Cargill names SE3.

Are ester-filled transformers mandatory in solar parks or for battery storage?

No, there is no general requirement. Whether esters make sense depends on the fire protection concept, clearances, the insurer, proximity to water and the design. Documented examples include the solar projects of Enel Green Power in Spain and Sprng Energy in India.

Are natural esters non-hazardous to water when used close to water?

No. Under the AwSV (German Ordinance on Facilities for Handling Substances Hazardous to Water), natural esters such as FR3 and FR3r are considered generally hazardous to water (awg). Under § 13(1) AwSV, the facility requirements apply if entry into surface waters cannot be ruled out – which is precisely the case for floating PV and waterside sites.

More on this topic

Sources: IEC/IEEE 60076-16 Ed. 2.0 (2018), preview, VDE Verlag · IEC 60076-14:2013, webstore abstract · BLAK UmwS: Merkblatt Windenergieanlagen, as of 16 May 2023 (in German) · Cargill: Wind power (FR3) · Cargill: FR3 wind brochure ©2025 · Cargill: Solar power (FR3) · Cargill: Enel Green Power case study (PDF, ©2023) · Cargill: Sprng Energy solar case study (PDF, ©2023) · Cargill: NTPC case study (11 August 2023) · Cargill: Battery Energy Storage Systems · Cargill: SE3 fluid · Cargill: SE3 brochure ©2026 · Cargill: FR3r brochure ©2025 · AwSV § 13 (gesetze-im-internet.de, in German) · AwSV § 39 (gesetze-im-internet.de, in German) · mv-lub.de: Mineral oil or ester in the transformer? (water saturation)

FR3™, FR3r™ and SE3™ are trademarks of Cargill, Incorporated; Shell MIDEL is a trademark of Shell Brands International AG. The trademarks are used here solely to identify the original products. Vielhauer GmbH is an independent dealer. All technical data are typical values from the manufacturers’ documentation and standards (as of 11/2026) and do not constitute a specification; the current data sheet applies in each case.