Oil analysis in ester-filled transformers follows its own guidelines – IEC 62975 for natural and IEC 61203 for synthetic esters; water, viscosity, dissipation factor and gas analysis are evaluated differently than for mineral oil under IEC 60422.
For mineral transformer oil in service, IEC 60422 applies – more in our guide Testing transformer oil: oil analysis and DGA. For oil analysis in ester-filled transformers, there are separate guidelines:
Both IEC guidelines classify equipment into categories based on IEC 60422: category A for power transformers above 170 kV or with a critical supply function, B for above 72.5 to 170 kV, C for medium and low voltage up to 72.5 kV, and D to F for instrument transformers and tap changers. IEC 62975 additionally includes category O for 400 kV and above. According to both standards, operators may exclude small transformers up to 1 MVA and 36 kV from the classification.
Esters dissolve many times more water; according to Cargill, the saturation point of FR3 is around ten times higher than that of mineral oil. Absolute water limits for mineral oil therefore cannot be transferred. One example: for newly filled mineral oil transformers above 72.5 kV, IEC 60422 (2013 edition) specified a maximum of 10 mg/kg water, whereas IEC 62975 specifies less than 100 mg/kg for natural esters above 170 kV. As with mineral oil, measurement is carried out to IEC 60814 (Karl Fischer titration). For the evaluation, IEC 62975 contains a separate annex on water in esters, moisture equilibrium with the paper and the interpretation of relative saturation.
The acid number of esters is determined to IEC 62021-3, the method for non-mineral insulating liquids; for mineral oil, IEC 62021-1 applies. According to IEC 61203, esters age not only through oxidation but also through hydrolysis with water.
Natural esters oxidise much faster than mineral oil in air and thicken in the process. IEC 62975 lists viscosity as a routine test; in IEC 60422 it is not one of the routine tests. In a technical information sheet (R2080), Cargill recommends replacing the fluid if the viscosity has increased by more than 10 %, for FR3 to around 38 mm²/s at 40 °C. For synthetic esters, viscosity is a complementary test under IEC 61203.
Esters inherently have a higher dissipation factor: for new fluid at 25 °C, Cargill gives 0.20 % for natural ester compared with 0.05 % for mineral oil. For power factor measurements on complete transformers, Cargill advises doubling the limits customary for mineral oil until specific recommendations are available.
| Test | Method | Purpose | Group IEC 62975 / IEC 61203 |
|---|---|---|---|
| Colour and appearance | ISO 2049 | Ageing, turbidity, particles | Routine / routine |
| Breakdown voltage | IEC 60156 | Water and particles | Routine / routine |
| Water content | IEC 60814 | Moisture, conclusions about the paper | Routine / routine |
| Acidity | IEC 62021-3 | Oxidation and hydrolysis | Routine / routine |
| Dissipation factor (DDF) | IEC 60247 | polar ageing products, contaminants | Routine / routine |
| Viscosity | ISO 3104 | Oxidation, polymerisation | Routine / complementary |
| Dissolved gas analysis (DGA) | IEC 60567 | Tightness via air content; fault gases | Routine (tightness) / not in the test list |
| Fire point | ISO 2592 | Fire class, residual mineral oil after retrofilling | complementary / complementary |
| Interfacial tension | IEC 62961 | polar contaminants | complementary / complementary |
| Density | ISO 12185 | Identity, mixing | complementary / complementary |
| Additives (antioxidant) | IEC 60666 | Oxidation reserve | Special test / complementary |
| Particles | IEC 60970 | Contamination, wear | Special test / complementary |
| Miscibility, compatibility | ASTM D7752 and others | Topping up, retrofilling | Special test / special test |
Assignment according to Table 2 of both standards. Where more than one method is given, the reference method is shown here.
For esters in newly filled transformers before first energisation, both standards give recommendations in Table 3, graded by the highest voltage for equipment (up to 72.5 kV / above 72.5 to 170 kV / above 170 kV):
| Parameter | IEC 62975 (natural ester) | IEC 61203 (synthetic ester) |
|---|---|---|
| Breakdown voltage | > 55 / > 60 / > 60 kV | min. 55 / 60 / 60 kV |
| Water content | < 200 / < 150 / < 100 mg/kg | max. 200 / 150 / 100 mg/kg |
| Acidity | < 0.08 mg KOH/g | max. 0.08 mg KOH/g |
| Dissipation factor at 90 °C | < 0,07 | max. 0.1 |
| Fire point | > 300 °C | ≥ 300 °C |
| Viscosity at 40 °C | < 50 mm²/s | – |
| Total gas content | < 1.5 % (hermetically sealed, without nitrogen blanket) | – |
The water values are not temperature-corrected. According to IEC 62975, the maximum water content for natural esters below 72.5 kV should be agreed between supplier and user.
The “good – fair – poor” classification for esters in service is given in Table 5 of each standard and is only available in the text of the standard. According to its own statement, IEC 62975 is based on around 35,000 data sets from a large but young transformer population and advises caution in its application. As a published reference point, Cargill cites minimum breakdown voltages for aged fluid according to IEEE C57.147, measured to ASTM D1816 with a 2 mm gap (not comparable with IEC 60156): 40 kV up to 69 kV, 47 kV from 69 to below 230 kV, 50 kV from 230 kV.
For synthetic esters, IEC 61203 recommends routine tests every 1 to 2 years in category A, every 1 to 4 years in category B and every 1 to 12 years in category C, as well as after every filling before energising. Both standards point out that heavily loaded transformers need more frequent sampling. IEC 61203 also stresses that no action should be based on a single result – the trend is what counts.
The fault gases are the same as in mineral oil, but their quantities and ratios are not. IEC 60599 is written for mineral oil and, according to its scope, may only be applied with caution to other insulation systems. For esters, there is IEEE C57.155 and, since 2026, IEC 63585. According to the published summary of IEC 63585:
In IEC 62975, gas analysis as a routine test is geared towards checking tightness via the air content (oxygen and nitrogen). After a retrofill, every evaluation needs a new baseline sample.
Samples are taken to IEC 60475, to which IEC 62975 refers; Cargill names ASTM D923. Tell the laboratory which fluid is in the unit (FR3, FR3r, SE3 or a mixture) and whether and when it was converted – guideline values, gas patterns and dissipation factor differ from fluid to fluid. According to Cargill, laboratories without experience of FR3 should obtain test recommendations from the manufacturer.
We test ester fluids in our own laboratory – routine analyses, miscibility analyses before topping up and material compatibility tests. For you, this means that your samples are tested and evaluated as esters, not by mineral oil standards, and that for a retrofill, baseline and check values come from a single source. We agree with you which tests you need. We offer free qualification programmes for equipment, and technical data sheets and safety data sheets are available on request.
Ester fluids from Vielhauer GmbH
Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.
IEC 62975:2021 applies to natural esters such as Cargill FR3 and FR3r, and IEC 61203:2025 to synthetic esters such as Cargill SE3. For interpreting dissolved gas analysis, there is IEEE C57.155 and, since 2026, IEC 63585. IEC 60422 is written for mineral oil.
Esters dissolve many times more water; according to Cargill, the saturation point of FR3 is around ten times higher than that of mineral oil. A water content that already indicates wet mineral oil may be uncritical for esters. What counts are the guideline values in the ester standards and the relative saturation.
Only to a limited extent. According to its scope, IEC 60599 may only be applied with caution to other insulation systems. Natural esters form ethane and hydrogen even without a fault, so IEC 63585 uses its own ratios, trends and Duval Triangles 3 and Duval Pentagons 3 for esters.
For synthetic esters, IEC 61203 recommends routine tests every 1 to 2 years in category A, every 1 to 4 years in category B and every 1 to 12 years in category C, as well as after every filling before energising. Heavily loaded transformers and abnormal values justify shorter intervals.
For natural esters in newly filled transformers, IEC 62975 recommends more than 55 kV up to 72.5 kV and more than 60 kV above that. For synthetic esters, IEC 61203 gives at least 55 and 60 kV respectively. Measurement is carried out to IEC 60156.
Sources: IEC 62975:2021 – preview (scope, Tables 1–3, clause 7) · IEC 62975:2021 – preview, VDE Verlag (table of contents) · IEC 61203:2025 – preview (Tables 1–4, clause 7) · IEC 61203:2025 – preview, VDE Verlag (foreword, introduction) · IEC 60599:2022 – preview, VDE Verlag (scope) · prEN IEC 63585:2025 / EN IEC 63585:2026 – catalogue entry with summary (iTeh) · IEC 63585:2026 – catalogue entry, EVS · DIN EN IEC 63585 (VDE 0370-3585):2026-09, draft – DIN Media · IEEE C57.155-2014 – abstract (GlobalSpec) · IEEE PC57.155 – project page (PAR 2021) · Cargill: Envirotemp FR3 Fluid R2000 (10/2016), section Fluid Maintenance · Cargill: Transformer power factor and FR3 fluid (R2100, 8/2020) · Cargill: Thin Film Oxidation (R2080, 10/2013) · Cargill: FR3 Fluid Storage and Handling Guide (S10, 8/2020) · Cargill: FR3 fluid retrofill brochure (©2024) · mv-lub.de: Testing transformer oil – oil analysis and DGA (IEC 60422)
FR3™, FR3r™ and SE3™ are trademarks of Cargill, Incorporated; Shell MIDEL is a trademark of Shell Brands International AG. The trademarks are used here solely to identify the original products. Vielhauer GmbH is an independent dealer. All technical data are typical values from the manufacturers’ documentation and standards (as of 11/2026) and do not constitute a specification; the current data sheet applies in each case.