Buy Cargill FR3, FR3r and SE3: pack sizes from 1 litre to road tanker, delivery across Europe

Natural and synthetic ester transformer fluids in seven pack sizes – from 1-litre containers for samples and topping up to bulk deliveries by road tanker, delivered across Europe with our own logistics.

Buy FR3, FR3r and SE3 – what we supply

As an independent dealer, we supply Cargill’s three ester fluids in original quality. Which ester is right depends mainly on the transformer design and the temperatures at the site:

ProductType and standardPour point (typical)Typical use
Cargill FR3soybean-based natural ester, IEC 62770−21 °Chermetically sealed distribution and power transformers, retrofilling
Cargill FR3rrapeseed-based natural ester, IEC 62770−33 °Cas FR3, where lower temperatures are expected at the site
Cargill SE3synthetic ester, IEC 61099below −50 °Cfree-breathing transformers, very cold sites

All three are K-class fluids with a fire point above 300 °C. You will find a detailed comparison in Ester fluids for transformers.

Pack sizes: from 1 litre to road tanker

We supply FR3, FR3r and SE3 in seven pack sizes. Availability and lead time depend on the product, quantity and delivery address, and we will state them in our quotation.

Pack sizesContentsSuitable for
Small container1 lSamples, laboratory comparisons, material compatibility tests, topping up very small quantities
Can8 lTopping up during maintenance, instrument transformers and small equipment
Can20 l and 25 lWorkshop and service, topping up distribution transformers
Drum200 lFilling individual distribution transformers, reserve stock
IBC1,000 lSeries production, retrofilling several units
Road tankerbulkPower transformers, large retrofilling projects, transformer manufacturers

Opened containers should be kept under dry nitrogen, because natural esters age in contact with air. You will find guidance in Storing and handling ester fluids.

Delivery across Europe

We deliver across Europe with our own logistics from Leverkusen – to grid operators, municipal utilities, transformer manufacturers, service companies and industrial plants. According to the safety data sheets, FR3, FR3r and SE3 are not dangerous goods for transport. For deliveries within Germany, please note the classification under the AwSV (German Ordinance on Facilities for Handling Substances Hazardous to Water): natural esters such as FR3 and FR3r are considered generally hazardous to water (awg); more in AwSV, WGK and disposal (Germany).

How your enquiry works

  1. Tell us what you need: product (or application, if you are not yet sure), quantity, pack size and delivery address.
  2. Quotation: we check availability and lead time and send you a quotation with the current data sheets.
  3. Optional testing: for retrofilling or topping up, we test samples in our laboratory beforehand, for example for miscibility and material compatibility.
  4. Delivery: across Europe with our own logistics, in the pack size you require.

Request data sheets and safety data sheets

For tenders, approvals and risk assessments, we will send you the current technical data sheets and safety data sheets for FR3, FR3r and SE3. Just tell us the product and the language you require. For tenders, we recommend always taking properties together with the test method from the current data sheet – typical values are not a specification.

What else we offer

Ester fluids from Vielhauer GmbH

  • Delivery across Europe with our own logistics – 1 l, 8 l, 20 l, 25 l, drums (200 l), IBCs (1,000 l) and bulk by road tanker; availability and lead time on request
  • Our own laboratory for ester fluids: oil analyses, miscibility analyses and material compatibility tests
  • Retrofilling support from sampling through to the check after conversion
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request
  • Pack sizes, delivery and how to order: Buy FR3, FR3r and SE3

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Frequently asked questions

Can I buy Cargill FR3 in small quantities?

Yes. We supply FR3, FR3r and SE3 from a 1-litre container upwards, as well as in 8 l, 20 l and 25 l, in 200 l drums, in 1,000 l IBCs and in bulk by road tanker. Small containers are suitable for samples, laboratory comparisons and topping up small quantities.

Do you deliver FR3, FR3r and SE3 outside Germany?

Yes, we deliver across Europe with our own logistics. We will state availability and lead time in our quotation, because they depend on the product, quantity, pack size and delivery address.

Are FR3, FR3r and SE3 dangerous goods?

No, according to the safety data sheets, the three ester fluids are not dangerous goods for transport. In Germany, natural esters such as FR3 and FR3r are considered generally hazardous to water (awg) under the AwSV (German Ordinance on Facilities for Handling Substances Hazardous to Water); for SE3, we will provide the classification on request.

Can I get data sheets and safety data sheets?

Yes. We will send you the current technical data sheets and safety data sheets on request, together with the quotation if you wish. Please tell us the language you require.

Is Vielhauer GmbH a Cargill distribution partner?

No. Vielhauer GmbH is an independent dealer and supplies the original Cargill products FR3, FR3r and SE3. We use the trademarks solely to identify these products.

Which ester is right for my transformer?

For hermetically sealed transformers, FR3 or FR3r is usual, FR3r where lower temperatures occur at the site. For free-breathing transformers and very cold sites, the synthetic ester SE3 is the obvious choice. If in doubt, we will advise you and test samples in our laboratory.

More on this topic

FR3™, FR3r™ and SE3™ are trademarks of Cargill, Incorporated; Shell MIDEL is a trademark of Shell Brands International AG. The trademarks are used here solely to identify the original products. Vielhauer GmbH is an independent dealer. All technical data are typical values from the manufacturers’ documentation and standards (as of 11/2026) and do not constitute a specification; the current data sheet applies in each case.