Data centre transformers: esters for fire safety and load reserve

A data centre transformer filled with ester insulating fluid meets K-class requirements, can be installed with smaller clearances under IEC 61936-1 and, according to Cargill, can carry up to 20 % more load than mineral oil in emergency operation when filled with FR3.

Why data centres use ester-filled transformers

A data centre needs high power in a small space and as close to the load as possible. Medium-voltage transformers are therefore often located directly at or inside the building, next to switchgear, UPS systems and cable routes. The question “Data centre transformer: ester or mineral oil?” mainly comes down to three points: fire safety, loading capability and space. Ester fluids such as Cargill FR3, FR3r and SE3 address exactly these points.

Fire safety: K-class instead of O-class

IEC 61039 classifies insulating liquids by their fire point: O-class up to 300 °C, K-class above 300 °C. According to Cargill’s data sheets, the fire point (ISO 2592) is 350–360 °C for FR3, 360 °C for FR3r and above 305 °C for SE3. For mineral oil, Cargill gives around 160–165 °C. The fire point should not be confused with the flash point, which is lower for all three esters (around 260 °C).

Cargill also describes FR3 as self-extinguishing: once ignited, the fluid does not continue to burn. According to Cargill, FR3 is FM Global approved and UL classified; Cargill states that FM Global recognises FR3 for most installations as a safeguard equivalent to spatial separation, fire walls and fire suppression systems – based on ignition tests with hot metal and electric arcs. For insurers and fire protection planners, this evidence is often the decisive point. More in Fire safety with ester fluids.

Installation close to the load

The installation standard IEC 61936-1 (in Germany DIN EN IEC 61936-1, VDE 0101-1, the German adoption of the standard) differentiates the minimum clearances for outdoor transformers by liquid class and liquid volume. In IEC 61936-1:2010 with Amendment 1:2014, Table 3 specifies, for example, for oil-insulated transformers (O) with a liquid volume of 2,000 to less than 20,000 l a clearance of 5 m to other transformers or non-combustible building surfaces and 10 m to combustible building surfaces. For K-class liquids without enhanced protection and 1,000 to less than 3,800 l, the figures are 1.5 m and 7.5 m respectively; with enhanced protection (tank rupture strength, pressure relief, fault protection) 0.9 m horizontally and 1.5 m vertically.

On a data centre campus, shorter clearances mean shorter cable runs and less space for fire walls. The version applicable in Germany, DIN EN IEC 61936-1 (VDE 0101-1):2023-02, may differ; the valid version of the standard and the project’s fire protection concept always apply. For projects in the USA, the National Electrical Code (NEC 450.23) permits indoor installation of transformers with “less-flammable” liquid without a conventional transformer vault under certain conditions.

Higher loading capability with thermally upgraded paper

For data centres, the reserve during load peaks and in the (n-1) case is what counts. Cargill states that FR3 can carry up to 20 % more load than mineral oil in emergency operation without compromising reliability. This is based on its thermal behaviour: according to Cargill, a transformer with thermally upgraded paper (TUK) and FR3 can be operated 15 to 20 °C hotter and achieve thermal class 140; Cargill refers to IEC 60076-14 and IEEE C57.154. According to Cargill, FR3 and FR3r are designed for top-oil temperatures of up to 140 °C.

IEC 60076-14 (2013 edition) applies to liquid-immersed power transformers with high-temperature insulation materials or combinations of high-temperature and conventional insulation operated above the usual temperature limits. This reserve therefore does not result automatically from the fluid but from the design of the transformer. It must be confirmed by the manufacturer.

Space and design

Cargill names two options: for the same load, a more compact transformer can be chosen, or for the same size, more load is available. According to Cargill, FR3 also extends the life of the paper insulation; in accelerated ageing tests to IEEE C57.100, the paper lasted five to eight times longer than in mineral oil.

Documented examples

Specific data centre projects are rarely named publicly together with the insulating fluid. One documented example: in a press release from January 2026, the Italian transformer manufacturer GBE S.p.A. reports a delivery for a data centre in Northern Europe comprising 20 transformers of 6 MVA and 43 transformers of 3.15 MVA, filled with Cargill FR3. The release does not name the operator or the site. Cargill’s own data centre brochure does not name any projects; we will only list further examples here once they are documented.

Data centre requirements and matching ester properties

RequirementProperty of the ester fluidSource
Fire safety, K-classFire point FR3 350–360 °C, FR3r 360 °C, SE3 > 305 °C (ISO 2592); K-class limit 300 °CCargill data sheets; IEC 61039
Evidence for insurersFR3 FM Global approved and UL classified, according to CargillCargill, “Fire safety” page
Small clearances, installation at the buildingSmaller minimum clearances for K-class liquids than for O-class liquidsIEC 61936-1:2010/AMD1:2014, Table 3
Load reserve in emergency operationFR3 up to 20 % more load than mineral oilCargill, data centre page and brochure
High operating temperatureWith TUK paper thermal class 140, operation 15–20 °C hotter; top oil up to 140 °CCargill, FR3 technical details; IEC 60076-14
Moisture tolerance of the insulationWater saturation at 20 °C: natural ester approx. 1,100 ppm, mineral oil approx. 55 ppmMineral oil or ester
Free-breathing transformerSE3 suitable according to Cargill; FR3 only with limited air ingressCargill SE3 and FR3 documentation
Water protection (German AwSV)FR3, FR3r: generally hazardous to water (awg); no hazard level under § 39(11) AwSVCargill safety data sheets; AwSV

What planners should consider

Standards and fluid

  • Specification: natural esters to IEC 62770 (FR3, FR3r), synthetic esters to IEC 61099 (SE3). The standard belongs in the tender, not just the product name.
  • Design: Cargill recommends FR3 for hermetically sealed transformers. For free-breathing units with an open conservator, Cargill names SE3.
  • Engineering: esters are more viscous than mineral oil (FR3 32–34 mm²/s at 40 °C). The transformer manufacturer designs the cooling and cooling ducts for the selected fluid.

Insurers and approval

  • Clarify early on which evidence your property insurer requires, for example FM approval of the fluid and the transformer.
  • Clearances, fire compartments and doors are governed by DIN EN IEC 61936-1 (VDE 0101-1) and the fire protection concept.
  • Under the AwSV (German Ordinance on Facilities for Handling Substances Hazardous to Water), natural esters are generally hazardous to water (awg; vegetable oils, UBA Kenn-Nr. 9442, the identification number published by the German Environment Agency). Under § 13(1) AwSV, the facility requirements for floating substances apply if entry into surface waters cannot be ruled out. Agree the containment with the competent authority. More in Disposal, AwSV and WGK (Germany).

Operation and maintenance

  • For monitoring natural esters, IEC 62975 specifies tests and evaluation guidance. Limit values for mineral oil cannot be transferred directly; for water, the relative saturation is what counts.
  • Keep reserve fluid tightly closed and dry, and in tanks under nitrogen. Cargill recommends storage temperatures of 10–40 °C.
  • When topping up: FR3 is miscible with mineral oil but not with silicone oil. When converting existing equipment, Cargill recommends no more than 7 % residual mineral oil.

What this means for your data centre project

Whether an ester-filled transformer makes sense for your data centre is decided jointly by the fire protection concept, the insurer and the transformer design. The fluid itself is the component that is easiest to specify clearly.

As an independent dealer, Vielhauer GmbH supplies Cargill FR3, FR3r and SE3 across Europe with its own logistics: from 1 l containers for samples through 20 l and 25 l cans and 200 l drums to 1,000 l IBCs and bulk by road tanker. Availability and lead time on request. We will send you technical data sheets and safety data sheets for your insurer and the approval process. In our own laboratory, we test oil samples, miscibility and material compatibility; for existing mineral oil transformers, we support retrofilling from sampling through to the check after conversion. We offer free qualification programmes for your equipment. Contact us via our contact form.

Ester fluids from Vielhauer GmbH

  • Delivery across Europe with our own logistics – 1 l, 8 l, 20 l, 25 l, drums (200 l), IBCs (1,000 l) and bulk by road tanker; availability and lead time on request
  • Our own laboratory for ester fluids: oil analyses, miscibility analyses and material compatibility tests
  • Retrofilling support from sampling through to the check after conversion
  • Qualification programmes for your equipment are offered free of charge
  • Current technical data sheets and safety data sheets are available on request
  • Pack sizes, delivery and how to order: Buy FR3, FR3r and SE3

Enquiries to info@mv-lub.de, phone +49 2236 322450, or via our contact form.

Frequently asked questions

Why are ester-filled transformers used in data centres?

Mainly because of fire safety: ester fluids such as Cargill FR3, FR3r and SE3 have a fire point above 300 °C and are therefore K-class under IEC 61039. Under IEC 61936-1, this allows smaller clearances and makes installation close to the building easier. According to Cargill, FR3 also provides a load reserve of up to 20 % compared with mineral oil.

Which ester fluid is right for a data centre transformer?

For hermetically sealed transformers, Cargill recommends the natural esters FR3 or FR3r. For free-breathing transformers with an open conservator, Cargill names the synthetic ester SE3. The final choice is made by the transformer manufacturer together with the design.

Does a K-class fluid replace fire walls or fire suppression systems?

Not automatically. According to Cargill, FM Global recognises FR3 for most installations as a safeguard equivalent to clearances, fire walls and fire suppression systems. Whether this applies to your project is decided by the fire protection concept, the authority and the insurer.

Does an ester-filled transformer automatically deliver 20 % more power?

No. Cargill states up to 20 % more loading capability compared with mineral oil, and thermal class 140 with thermally upgraded paper. This reserve requires a suitable design to IEC 60076-14 and must be confirmed by the transformer manufacturer.

Are ester fluids in data centres hazardous to water?

Under the AwSV (German Ordinance on Facilities for Handling Substances Hazardous to Water), natural esters such as FR3 and FR3r are considered generally hazardous to water (awg). Under § 39(11) AwSV, facilities with awg substances are not assigned a hazard level. Clarify the containment requirements with the competent authority.

More on this topic

Sources: Cargill: FR3 Fluid for Data Centers · Cargill: FR3 fluid data center brochure (PDF) · Cargill: Higher flash and fire points for improved fire safety · Cargill: FR3 fluid technical details (TUK, thermal class 140, IEC 60076-14) · Cargill: FR3 fluid brochure ©2025 · Cargill: Battery Energy Storage Systems (FM equivalency, TUK) · Cargill: SE3 brochure ©2026 · IEC 61936-1:2010/AMD1:2014, preview (Table 3) · IEC 60076-14:2013, webstore abstract · IEC 62975:2021, abstract (Standards Norway) · Consulting-Specifying Engineer: A game-changing transformer dielectric fluid (NEC 450.23) · GBE S.p.A.: High efficiency transformers for data centers (press release, 21 January 2026) · AwSV § 39 (gesetze-im-internet.de, in German) · AwSV § 13 (gesetze-im-internet.de, in German) · mv-lub.de: Mineral oil or ester in the transformer?

FR3™, FR3r™ and SE3™ are trademarks of Cargill, Incorporated; Shell MIDEL is a trademark of Shell Brands International AG. The trademarks are used here solely to identify the original products. Vielhauer GmbH is an independent dealer. All technical data are typical values from the manufacturers’ documentation and standards (as of 11/2026) and do not constitute a specification; the current data sheet applies in each case.